LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 11

Advertising
background image

LAARS Heating Systems

Page 10

Pennant 200, 300, 400

Page 11

from one appliance trips due to excessive stack spill

or back pressure indicating a blocked vent condition,

that all appliances attached to the vent be locked out

and prevented from operating. Note that the Pennant

is equipped with a blocked vent safety (pressure)

switch, as shipped. However, this safety switch has

only been designed and tested to be effective in

installations where the Pennant is vented separately

and NOT common vented with other appliances. As an

additional precaution, it is recommended that a Carbon

Monoxide (CO) alarm be installed in all enclosed

spaces containing combustion appliances. If assistance

is required in determining how a blocked vent safety

system should be connected to a LAARS product,

please call Applications Engineering at the Rochester

phone number on the back cover of this manual.

Refer to the installation and operating

instructions on all appliances to be common vented

for instructions, warnings, restrictions and safety

requirements. If safe operation of all appliances

connected to a common vent cannot be assured,

including prevention of spillage of flue gases into

living spaces, common venting should not be applied,

and appliances should each be vented separately.

2.2.4 Category III Vent

When the Pennant is vented with horizontal

discharge, it must be installed per this installation

manual and the venting system manufacturer’s

installation instructions. The vent system must be

sealed stainless steel, per Table 5.

50 linear feet (15.2m) of pipe. Subtract 10 allowable

linear feet (3.0m) for every additional elbow used.

2.3 Locating Vent & Combustion Air

Terminals

2.3.1 Side Wall Vent Terminal

The appropriate Laars side wall vent terminal

must be used, and is listed in the installation and

operation manual. The terminal provides a means of

installing the vent piping through the building wall,

and must be located in accordance with ANSI Z223.1/

NFPA 54 and applicable local codes. In Canada, the

installation must be in accordance with CSA B149.1

and local applicable codes. Consider the following

when installing the terminal:

1. Figure 3 shows the requirements for mechanical

vent terminal clearances for the U.S. and Canada.

2. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

3. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows,

gravity inlets or other openings. Whenever

possible, locations under windows or near doors

should be avoided.

4. Locate the vent terminal so that it cannot be

blocked by snow. The installer may determine

that a vent terminal must be higher than the

minimum shown in codes, depending upon local

conditions.

5. Locate the terminal so the vent exhaust does

not settle on building surfaces or other nearby

objects. Vent products may damage such surfaces

or objects.

6. If the boiler or water heater uses ducted

combustion air from an intake terminal located

on the same wall, locate the vent terminal at least

3 feet (0.9m) horizontally from the combustion

air terminal, and locate the vent terminal at least

1 foot (0.3m) above the combustion air terminal.

WARNING

The outdoor vent terminal gets hot. Unit must be

installed in such a way as to reduce the risk of

burns from contact with the vent terminal.

AVERTISSEMENT

La sortie d’évent à l’extérieur devient très chaude.

Elle doit être installée de façon à réduire le risque

de brûlures au contact de l’extrémité de l’évent.

Term

Description

Pipe

Must comply with UL Standard 1738 such

as Type AL29-4C Stainless Steel

(either insulated or non-insulated).

Joint

Sealing

Follow vent manufacturer's instructions.

Table 5. Required Horizontal Venting Material.

Route the vent pipe to the heater as directly as

possible. Seal all joints and provide adequate hangers

as required in the venting system manufacturer’s

installation instructions. Horizontal portions of the

venting system must be supported to prevent sagging

and may not have any low sections that could trap

condensate.

The unit must not support the weight of the vent

pipe. Horizontal runs must slope downwards not less

than 1⁄4 inch per foot (2 cm/m) from the unit to the vent

terminal.

L’appareil ne doit pas supporter le poids de la

gaine d’évent. Les parties horizontales doivent être

installées avec une pente de 2 cm/m (1/4 inch par pied)

descendant de l’appareil vers la sortie de l’évent.

Reference Table 1 for the size of the Category

III vent system. Up to three elbows can be used with

Advertising