Laars heating systems – LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 18

Advertising
background image

LAARS Heating Systems

Page 16

Pennant 200, 300, 400

Page 17

Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System.

SYSTEM PUMP

MAKE-UP

COLD WATER

PUMP LOCATION FOR

PUMP-MOUNTED UNITS

PRIMARY/SECONDARY MANDATORY FOR ALL

VARIABLE FLOW SYSTEMS
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR

PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)

BOILER CIRCUIT PIPING MUST BE EQUAL

TO BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE

MUST BE AT LEAST 120°F.

C

C

C

C

180°F

180°F

150°F

130°F

NOTES:

1. BOILER LOOP IN EXAMPLE IS MAINTAINED AT 180°F.

2. ZONE THERMOSTATS CAN BE INTERLOCKED WITH BOILER,

SO THAT BOILER FIRES UPON CALL FOR HEAT FROM ANY

ZONE.

3. ZONE PIPING AND INTERLOCK WIRING TO BE DESIGNED

BY SYSTEM ENGINEER.

CAUTION: THIS DRAWING SHOWS SUGGESTED

PIPING CONFIGURATION AND VALVING, CHECK

WITH LOCAL CODES AND ORDINANCES FOR

ADDITIONAL REQUIREMENTS.

CHECK VALVE

TEMPERATURE

SENSOR

VALVE

PURGE VALVE

THERMOMETER

GLOBE VALVE

EXPANSION TANK

WITH AIR SCOOP AND

AUTO AIR VENT

PUMP

PRESSURE REDUCING VALVE

W/ FAST FILL BYPASS

3-WAY VALVE

Figure 7. Hydronic Piping — Primary-Secondary, Reverse-Return.

CAUTION: THIS DRAWING SHOWS SUGGESTED

PIPING CONFIGURATION AND VALVING, CHECK

WITH LOCAL CODES AND ORDINANCES FOR

ADDITIONAL REQUIREMENTS.

C

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR
PUMP-MOUNTED UNITS

RETURN

SYSTEM

PRIMARY/SECONDARY MANDATORY FOR ALL

VARIABLE FLOW SYSTEMS
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM

PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR

PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)
BOILER CIRCUIT PIPING MUST BE EQUAL

TO BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER

DOTTED DEVICES INDICATE ALTERNATE LOCATIONS

PUT BOILER CONTROL SENSOR IN THE SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE

MUST BE AT LEAST 120°F.

CHECK VALVE

TEMPERATURE

SENSOR

VALVE

PURGE VALVE

THERMOMETER

GLOBE VALVE

EXPANSION TANK

WITH AIR SCOOP AND

AUTO AIR VENT

PUMP

PRESSURE REDUCING VALVE

W/ FAST FILL BYPASS

3-WAY VALVE