LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 33

Advertising
background image

LAARS Heating Systems

Page 32

Pennant 200, 300, 400

Page 33

for ignition. If the ignition control locks out, reset

by cycling the power off and on using the main

power switch on the right side of the cabinet.

6. When the unit is running, the supply gas pressure

must be checked. Inlet gas pressure must not

exceed 13 in. w.c. (3.2 kPa). The minimum inlet

gas pressure is 5 in. w.c. (1.2 kPa) and 8 in. w.c.

(2 kPa) for LP.

7. Once the inlet gas pressure is verified, the

outlet gas pressure from each valve (manifold

gas pressure) must be checked, and adjusted, if

necessary. The manifold gas pressure must be 3.0

in. w.c. (0.62 kPa) for natural gas and 9.0 in. w.c.

(2.2 kPa) for LP.

8. Complete the setup by checking the CO

2

at the

outlet of the unit. The CO

2

should be 8% for

natural gas, or 9.2% for LP.

9. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested

.

To test:

(a) Close gas shutoff valve with burner

operating.

(b) The flame will go out and blower will

continue to run for the post purge cycle.

Three attempts to light will follow. Ignition

will not occur as the gas is off. The ignition

control will lockout, and will have to be

reset by cycling the power before the unit

will operate.

(c) Open gas shutoff valve. Restart the

appliance. The ignition sequence will

start again and the burner will start. The

appliance will return to its previous mode

of operation.

6.7.2 High Altitude Adjustment and

Set-Up

High altitude adjustment must not be made on

appliances operating at elevations below 2500 ft. (762

m).

No orifice changes are required to adjust the

Pennant appliances for high altitude. High altitude

adjustment is accomplished by adjustment of the air

shutter. A CO

2

or O

2

analyzer is required to make these

adjustments.

Start the adjustment process by checking the CO

2

in the “as installed” condition. Adjust the air shutter(s)

so that the CO

2

is about 8% or the O

2

is about 6.8%

for appliances operating on natural gas. For appliances

operating on LP Gas adjust the air shutter(s) so that the

CO

2

is about 9.2% or the O

2

is about 6.8%.

If the appropriate CO

2

/ O

2

levels cannot be

achieved by adjusting the air shutter. Contact the

Technical Services Department at (800) 900-9276.

The amount of derate will vary depending on

heating value of the fuel and the elevation at the

installation site.

Caution

Should any odor of gas be detected, or if the gas

burner does not appear to be functioning in a

normal manner, close main shutoff valve, do not

shut off switch, and contact your heating contractor,

gas company, or factory representative.

Attention

Si vous sentez une odeur de gaz ou si le brûleur

à gaz ne parait pas fonctionner de manière

normale, fermez la vanne d’isolement, ne fermez

aucun interrupteur, et appelez votre entreprise de

chauffage, la compagnie de gaz ou un représentant
du fabricant..

6.8 Shutting Down the Pennant

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. If freezing is anticipated, drain the Pennant and

be sure to also protect building piping from

freezing.

This step to be performed by a qualified

service person.

6.9 To Restart the Pennant

If drained, follow Section 6.1 in this manual for

proper filling and purging.

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. WAIT FIVE (5) MINUTES.

4. Set the aquastat or thermostat to its lowest

setting.

5. Open all manual gas valves.

6. Reset all safety switches (pressure switch,

manual reset high limit, etc.).

7. Set the temperature controller to the desired

temperature setting and switch on electrical

power.

8. Burner will go through a pre-purge period and

ignitor warm-up period, followed by ignition.

SECTION 7.

Maintenance

7.1 System Maintenance

1. Lubricate the system water-circulating pump, if

required, per the instructions on the pump.

2. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.

3. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean

the screens in the vent terminal and combustion

air terminal (when used).

Advertising
This manual is related to the following products: