Figure 4. Hydronic Piping — Multiple Boilers, Primary Secondary System.

PRIMARY/SECONDARY MANDATORY FOR ALL

VARIABLE FLOW SYSTEMS

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS

DIMENSION "C" (COMMON PIPING) TO BE FOUR

PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)
BOILER CIRCUIT PIPING MUST BE EQUAL

TO BOILER WATER CONNECTION SIZE

BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM

C

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR

PUMP-MOUNTED UNITS

RETURN

SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE

MUST BE AT LEAST 120°F.

C

CAUTION: THIS DRAWING SHOWS SUGGESTED

PIPING CONFIGURATION AND VALVING, CHECK

WITH LOCAL CODES AND ORDINANCES FOR

ADDITIONAL REQUIREMENTS.

CHECK VALVE

TEMPERATURE

SENSOR

VALVE

PURGE VALVE

THERMOMETER

GLOBE VALVE

EXPANSION TANK

WITH AIR SCOOP AND

AUTO AIR VENT

PUMP

PRESSURE REDUCING VALVE

W/ FAST FILL BYPASS

3-WAY VALVE

Figure 5. Hydronic Piping — Multiple Boilers, Low Temperature System.

C

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR

PUMP-MOUNTED UNITS

RETURN

SYSTEM

PRIMARY/SECONDARY MANDATORY FOR ALL

VARIABLE FLOW SYSTEMS

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR

PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)

BOILER CIRCUIT PIPING MUST BE EQUAL

TO BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE

MUST BE AT LEAST 120°F.

C

ADJUSTMENT PROCEDURE TO MAINTAIN

120°F INLET TEMP:

1. Turn on boiler and open valves A & B.

2. After steady-state operation, if T1 is less

than

slowly close valve B until T1

climbs to 120°F.

3. If T1 is greater than 120°F, slowly close

until T1 drops to 120°F.

4. Check after system operating temperature

has stabilized. Make final adjustments.

120°F,

valve A

A

B

T1

B

A

T1

CHECK VALVE

TEMPERATURE

SENSOR

VALVE

PURGE VALVE

THERMOMETER

GLOBE VALVE

EXPANSION TANK

WITH AIR SCOOP AND

AUTO AIR VENT

PUMP

PRESSURE REDUCING VALVE

W/ FAST FILL BYPASS

3-WAY VALVE

CAUTION: THIS DRAWING SHOWS SUGGESTED

PIPING CONFIGURATION AND VALVING, CHECK

WITH LOCAL CODES AND ORDINANCES FOR

ADDITIONAL REQUIREMENTS.