LAARS Heating Systems

Page 32

Pennant 200, 300, 400

Page 33

k. Flow switch

l. Gas train

m. Control components

7.2.1 Burners

Close main manual gas valve before proceeding.

Checking the burners for debris - Remove the ignitor/

burner access panel and ignitor, and inspect the

burners through the ignitor hole using a flashlight to

illuminate. If there is any indication of debris on the

burners that is visible, all the burners will need to be

inspected more thoroughly. Remove the gas manifold

assemblies and the burner assemblies. Inspect the

burners. Clean burners, if necessary, by blowing

compressed air from the outside of the burners into

the center of the burner. A dirty burner may be an

indication of improper combustion or dirty combustion

air. Determine the cause, and correct. Replace the

burners in the reverse order.

7.2.2 Filter

The filter used in the Pennant is washable and has

an 80% arrestance rating. Since the filter is washable,

it will only need replacement occasionally. If filter

replacement is needed, it should only be replaced with

a factory part. Inspect the air filter monthly, or more

often in dirty environments. If there is debris on the

air filter, remove it from the filter frame, and wash

it with mild soap and water. Ensure that the filter is

completely dry before reinstalling.

7.2.3 Gas Valves

The gas valves are designed to operate with

supply pressures of 4-13 in. w.c. (1.0 to 3.2 kPa).

To remove a valve, shut off 120-volt power

and the manual gas shutoff valve. Remove the front

panels from the unit. Disconnect the wires to the valve.

Disengage the unions before and after the valve, and

remove the valve. Pull the pipe nipples from the inlet

and outlet of the valve, and clean the threads on the

pipe nipples for reuse. Apply new tape or pipe dope

to the pipe nipples (threaded joints should be coated

with piping compound resistant to action of liquefied

petroleum gas), and reinstall in reverse order. Turn

on manual gas shutoff valve and 120 volt power and

check appliance operation and tightness of gas valve

connections.

7.2.4 Manual Reset High Limit Control

The high limit switch is a manual reset, non-

adjustable switch with a remote bulb-type sensor.

Switches for water heaters and low temperature boiler

models are set at 200°F. Switches for standard boilers

are set at 240°F.

The control is located behind the front door, on a

panel in front of the blower. The probe is in the outlet

side of the header.

4. Keep the appliance area clear and free from

combustible materials, gasoline, and other

flammable vapors and liquids.

5. If the appliance is not going to be used for

extended periods in locations where freezing

normally occurs, it should be isolated from the

system and completely drained of all water. All

systems connected to it should also be drained or

protected from freezing.

6. Low water cutoffs, if installed, should be

checked every 6 months. Float type low water

cutoff should be flushed periodically.

7. Inspect flue passages, and clean with brushes/

vacuums, if necessary. Sooting in flue passages

indicates improper combustion. Determine the

cause and correct.

8. Inspect the vent system and air intake system,

and if the vent system is Category III, ensure

that all joints are sealed properly. If joints need

to be resealed, follow venting manufacturer's

instructions to clean and reseal vent system.

7.2 Appliance Maintenance and

Component Description

Only genuine Laars replacement parts should be used.

Caution

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing.

Attention

Lors d’entretien ou de réparation des commandes,

étiquetez tous les câbles avant de les déconnecter.

Des erreurs de câblage peuvent provoquer des

fonctionnements incorrects et dangereux. Après

toute intervention d’entretien ou de réparation,

vérifier que l’appareil fonctionne correctement.

The gas and electric controls on the appliance

are engineered for long life and dependable operation,

but the safety of the equipment depends on their

proper functioning. It is strongly recommended that

a qualified service technician inspect the basic items

listed below every year.

a. Ignition control

b. Ignitor

c. Water temperature control

d. Automatic gas valve

e. Pressure switches and tubing

f. Blower

g. High limit

h. Pump (if required)

i. Low water cutoff

j. Relays