Laars heating systems – LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 12

Advertising
background image

LAARS Heating Systems

Page 10

Pennant 200, 300, 400

Page 11

U.S. Installations (see note 1)

Canadian Installations (see note 2)

A= Clearance above grade, veranda, porch,

12 inches (30 cm)

12 inches (30 cm)

deck, or balcony

B= Clearance to window or door that may

Direct Vent Only: 12 inches (30 cm)

be opened

Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)

to side of opening; 1 foot (30 cm) above opening

C= Clearance to permanently closed window

See note 4

See note 5

D= Vertical clearance to ventilated soffit located

above the terminal within a horizontal

See note 4

See note 5

distance of 2 feet (61cm) from the center line of the terminal

E= Clearance to unventilated soffit

See note 4

See note 5

F= Clearance to outside corner

See note 4

See note 5

G= Clearance to inside corner

See note 4

See note 5

H= Clearance to each side of center line

See note 4

3 feet (91 cm) within a height 15 feet

extended above meter/regulator assembly

above the meter/regulator assembly

I= Clearance to service regulator vent outlet

See note 4

3 feet (91 cm)

J= Clearance to non mechanical air supply

Direct Vent Only: 12 inches (30 cm)

inlet to building or the combustion air inlet Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)

to any other appliance

to side of opening; 1 foot (30 cm) above opening

K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)

6 feet (1.83 m)

horizontally

L= Clearance above paved sidewalk or paved Vent termination not allowed in this location

Vent termination not allowed in this

driveway located on public property

location

M= Clearance under veranda, porch, deck,

See note 4

12 inches (30 cm) (see note 3)

or balcony

Notes:

1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of

the gas supplier.

5. For clearances not specified in CSA B149.1, clearance is in accordance with local installation codes and the requirements of the gas

supplier.

Figure 3. Vent Terminal Clearance.