LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 31

Advertising
background image

LAARS Heating Systems

Page 30

Pennant 200, 300, 400

Page 31

6.6.3 Changing Control Loop 1

Parameters

There are four parameters that affect the

operation of control loop 1. SP1 is the setpoint. td1

is the temperature differential. St2 is the stage 2

differential (when applicable) and Std is the stage 2

time delay. To change any of these parameters:

1. While the default temperature is displayed, press

and hold the upper and lower buttons together

until SEL is displayed.

2. Release the buttons, and CH1 will be displayed.

3. Within 30 seconds, press and hold the upper and

lower buttons together until the parameter you

want to change is displayed.

4. Release the buttons to displayed the value of that

parameter.

5. Within 30 seconds, press the upper button

to increase the value, or the lower button to

decrease the value of the parameter.

6. When the desired value is shown, stop pushing

the buttons. The revised value is effective

immediately.

7. In 30 seconds of button inactivity, the display

reverts back to the default temperature, and the

new value is stored in nonvolatile memory.

6.6.4 Enabling and Disabling Control

Loop 2

The Pennant must be told to recognize control

loop 2, which uses thermistor 2. To enable or disable

control loop 2:

1. While the default temperature is displayed, press

and hold the upper and lower buttons together

until SEL is displayed.

2. Release the buttons, and CH1 will be displayed.

3. Within 30 seconds, press the upper (or lower)

button. CH2 will be displayed.

4. Within 30 seconds, press and hold the upper and

lower buttons together until En2 is displayed.

5. Release the buttons. The current state, on or oFF,

will be displayed.

6. Within 30 seconds, press the upper (or lower)

button to toggle the En2 state, between on and

oFF.

7. When the desired state is shown (on for enable,

and oFF for disable), stop pushing the buttons.

The revised state is effective immediately.

8. In 30 seconds of button inactivity, the display

reverts back to the default temperature, and the

En2 selection is stored in nonvolatile memory.

6.6.5 Changing Control Loop 2

Parameters

There are five parameters that affect the

operation of control loop 1. En2 is the status. SP2 is

the setpoint. td2 is the temperature differential. ICE

St2 – Stage 2 temperature differential, for 2-stage

units. Factory default is 5°F (3°C). It is adjustable

from 0°F to 20°F (0°C to 11°C). Stage 2 (high fire) is

energized after the Std time delay, which begins when

the Pennant sensor reads less than or equal to SP1-td1-

St2. When set at 0°F/C, stage 2 is energized using only

the time delay Std.

Std – Stage 2 time delay. Default is 10 seconds.

It is adjustable from 0 to 300 seconds. Std and St2

work together to determine when stage 2 (high fire) is

activated on a two-stage unit.

Ch2 – Control loop 2 (thermistor 2). It is

accessed by pressing and holding the upper and lower

buttons, so that SEL appears, and then pressing one

of the buttons to scroll until Ch2 appears. This allows

programming access for the auxiliary thermistor.

En2 – Status of control loop 2, either on or off.

Default is on. Thermistor 2 will not be recognized

when En2 is off. (ICE and EP can override Ch2.)

SP2 – Control loop 2 (auxiliary) temperature

setpoint. Factory default is 180°F (82°C) for boilers,

and 125°F for water heaters. It is adjustable 35°F to

240°F (2°C to 116°C) for boilers and 65°F to 190°F

(18°C to 88°C) for water heaters. The Pennant is called

for heat and the auxiliary contacts are closed when

the temperature at the secondary sensor is less than or

equal to SP2-td2. The Pennant call for heat ends, and

the auxiliary contacts are opened when the temperature

at the secondary sensor is greater than, or equal to SP2.

td2 – Control loop 2 (auxiliary) temperature

setpoint differential. Factory default is 5°F (3°C). It

is adjustable from 2°F to 20°F (1°C to 11°C). This

defines the temperature below the setpoint that the

Pennant is called for heat and the auxiliary contacts are

closed on a fall in temperature.

ICE – Enables response from the low temperature

protection feature. It can be turned on or off, and the

default is on. When it is enabled, the Pennant is called

for heat and the auxiliary contacts are energized when

the temperature sensor detects less than 40°F (4°C),

and are de-energized when the temperature rises above

45°F (7°C).

EP – Enables the exerciser feature. It can be

turned on or off, and the default is on. When it is

enabled, the auxiliary contacts are closed for one

minute, if they have not been closed over the last 72

hours.

dEf – Default temperature display. Factory

default is rt1, which is the temperature at the Pennant

sensor (thermistor 1). The user may choose rt2, which

is the temperature at the auxiliary sensor (thermistor

2). To access this, press and hold both upper and lower

buttons. When “SEL” is displayed, press either the

upper or lower button, until “dEf” is displayed.

UnI – Allows the user to choose between °F and

°C. Factory default is °F. To access this, press and

hold both upper and lower buttons. When “SEL” is

displayed, press either the upper or lower button, until

“UnI” is displayed.

Advertising
This manual is related to the following products: