LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 30

Advertising
background image

LAARS Heating Systems

Page 28

Pennant 200, 300, 400

Page 29

Display Symbol

Function

Adjustment

Range

Factory

Default

Description

Main

Menu

Sub

Menu

°F1

(°C1)

Selected

Default

Temperature

Display (dEF)

N/A

°F1

°F1 indicates the temperature sensed by thermistor 1 is

normally displayed.

SEL

When the upper and lower buttons are pressed and

held, SEL is displayed, indicating that you are entering

the programming mode of the controller.

Ch1

SP1

Ch1

Temperature

Set Point

130°F to

220°F

(54°C to

104°C)

165°F

Stage 1 energized when the temperature is less than or

equal to SP1-td1.

td1

On/Off

Temperature

Differential

2°F to 20°F

(1°C to 11°C)

10°F

Stage 1 energized when the temperature is less than or

equal to SP1-td1.

St2

Stage 2

Temperature

Differential

0°F to 20°F

(0°C to 11°C)

5°F

As long as stage 1 is successful, stage 2 is energized

Std seconds after the temperature is less than or equal

to SP1-td1-St2. If St2=0, stage 2 is energized after the

Std time delay.

Std

Stage 2 Delay

0 to 300

seconds

10 s

As long as stage 1 is successful, stage 2 is energized

Std seconds after the temperature is less than or equal

to SP1-td1-St2. If St2=0, stage 2 is energized after the

Std time delay.

Ch2

En2

Status of Ch2

on or oFF

on

Enables or disables loop 2, so the Pennant control

knows whether or not to recognize that input.

SP2

Ch2

Temperature

Set Point

35°F to 240°F

(2°C to 116°C)

180°F

Auxiliary is energized when the temperature is less than

or equal to SP2-td2

td2

On/Off

Temperature

Differential

2°F to 20°F

(1°C to 11°C)

5°F

Auxiliary is energized when the temperature is less than

or equal to SP2-td2

ICE

Enable

response

to low temp

detection

on or oFF

on

Enables and disables the low temp assistance. Auxiliary

is energized when the temperature is less than 40°F

(4°C) and is de-energized when it is greater than 45°F

(7°C).

EP

Enable

auxiliary

exercise

on or oFF

on

Enables and disables the auxiliary exercise. When

EP=on, the auxiliary is energized for one minute if it has

not been energized over the last 72 hours.

dEF

Default

Temperature

Display

Selection

rt1 or rt2

Sensor

Temperature

rt1

Toggles between which sensor is used for the default

display temperature. rt1 is thermistor 1. rt2 is thermistor

2.

UnI

Units Selection

– Temperature

Scale

°F or °C

°F

Toggles between displaying values in °F and °C.

Table 11. Boiler Parameters