LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 27

Advertising
background image

LAARS Heating Systems

Page 26

Pennant 200, 300, 400

Page 27

15. After placing the unit in operation, the ignition

system safety shutoff device must be tested.

First, shut off the manual gas valve, and call

the unit for heat. After the pre-purge and ignitor

heat-up time, the main gas terminals will be

energized, attempting to light, for seven (7)

seconds, and then will de-energize. The unit will

attempt to light two more times, and then will go

into lockout mode. Second, turn the power off

and then on again, open the manual gas valve

and allow the unit to light. While the unit is

operating, close the manual gas valve and ensure

that power to the main gas valve has been cut.

16. Within three (3) days of start-up, recheck all air

bleeders and the expansion tank as described in

Steps 4 and 8 above.

Important: The installer is responsible for identifying

to the owner/operator the location of all emergency

shutoff devices.

WARNING

Do not use this appliance if any part has been

under water. Immediately call a qualified service

technician to inspect the appliance and to replace

any part of the control system and any gas control

that may have been under water.

AVERTISSEMENT

N’utilisez pas cet appareil si l’une de ses pièces

est passée sous l’eau. Appelez tout de suite un

technicien en entretien et en réparation pour

inspection de l’appareil et remplacement des

pièces du système de commande, et des pièces de

commande du circuit gaz, qui sont passées sous

l’eau.

6.2 Pennant Controller

Pennant 200-400 units feature a custom-

configured digital control system that is capable of

monitoring the temperature in two different loops.

Loop 1 is the Pennant loop, which uses thermistor

1, mounted in the inlet of the Pennant. Loop 2 is a

secondary loop, using the auxiliary thermistor (called

thermistor 2) provided loose with the Pennant.

Thermistor 2 can be installed where the user

chooses (in a tank, or in system piping, etc.) and is

connected to Pennant terminals 9 and 10. It is activated

in the Pennant controller menu (see section 6.6).

Auxiliary contacts in the Pennant controller will close

when Loop 2 calls for heat, and these contacts can be

used to energize a pump relay, or other device that the

user chooses.

6.3 Local / Remote Switch

A call for heat can be initiated by the Pennant

controller, or by an external controller. When an

external controller, such as a tank aquastat or multiple

boiler control, is used, it is connected between

Pennant terminals 3 and 4. With the switch in the

Remote position, the external controller is included

in the Pennant sequence of operation, and the Remote

indicator light on the front panel is illuminated. If

an external control is not used, put the switch in the

Local position, and terminals 3 and 4 are left out of the

sequence.

6.4 Sequence of Operation

The amber “Ready” light on the front panel

indicates that the control system is energized. Upon a

call for heat, the green “Call for Heat” indicator on the

front panel will light.

The pump time delay relay will receive a signal

to initiate. If the unit is pump-mounted, the pump

will be energized. The pump terminals on the field-

wiring terminals strip will energize a field pump that

is properly interlocked with the Pennant. The green

“Water Flow” indicator on the front panel will light,

once proper flow has been established by the water

flow switch.

Once the water flow switch makes, if all of the

safety interlocks are closed, the ignition module will

energize the blower(s) for a 15-second pre-purge,

followed by a 40-second period to allow the ignitor to

heat.

The ignition control energizes the blower. The

blower pressurizes the air box (which supplies air to

the burners) and closes the normally-open contact

on the airflow pressure switch. The blocked vent

pressure switch senses the pressure in the exhaust

plenum. This switch opens if the pressure is excessive

(as an indicator of a blocked vent). When these two

pressure switches are closed, voltage is sent to the

PSW terminal on the ignition control, which allows the

ignition module to proceed with the ignition sequence.

If the airflow proving circuit is not proven, the

ignition module will lock out, and the temperature

controller will display the air flow fault, AFF. The

ignition control LED will display its one-flash

sequence, as well. Section 6.5 describes the result of

air flow faults in more detail.

When the ignition control gets the signal at the

PSW terminal, it will energize its MV terminal, which

sends power to the stage one (or on/off) main valve.

The green Stage 1 indicator on the front panel will

light.

After a 7-second trial for ignition, the ignitor

switches to flame sense mode. If a flame is not

detected, the gas valve will close and the ignition

module will attempt ignition again (up to two more

times, for a total of three attempts.) If all three

attempts fail, the ignition control will lock out.

If flame is sensed, the burner will continue to

fire as long as there is a call for heat, and none of the

safety circuit is interrupted.

Advertising
This manual is related to the following products: