LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 16

Advertising
background image

LAARS Heating Systems

Page 14

Pennant 200, 300, 400

Page 15

5. Locate and install manual shutoff valves in

accordance with state and local requirements.

6. A sediment trap must be provided upstream of

the gas controls.

7. All threaded joints should be coated with

piping compound resistant to action of liquefied

petroleum gas.

8. The appliance and its individual shutoff valve

must be disconnected from the gas supply piping

during any pressure testing of that system at test

pressures in excess of 0.5 psig (3.45 kpa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas

supply piping system at test pressures equal to or

less than 0.5 psig (3.45 kpa).

10. The appliance and its gas connection must be

leak tested before placing it in operation.

11. Purge all air from gas lines.

WARNING

Do not use open flame to check for leaks. An open

flame could lead to explosion, which could result in

property damage, serious injury or death.

AVERTISSEMENT

Ne recherchez pas les fuites avec une flamme nue.

Une flamme nue peut provoquer une explosion qui

peut causer des dommages matériels, de sérieuses

blessures corporelles ou la mort.

NOTE: The Pennant appliance and all other gas

appliances sharing the gas supply line must be

firing at maximum capacity to properly measure

the inlet supply pressure. The pressure can be

measured at the supply pressure port on the gas

valve. Low gas pressure could be an indication of

an undersized gas meter, undersized gas supply

lines and/or an obstructed gas supply line.

SECTION 4A.

Water Connections —

Pennant Boiler

4A.1 Heating System Piping:

Hot Supply Connections — Boiler

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psig (82.7

kPa) static pressure at the boiler.

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

when rigid hangers are installed. Maintain 1" clearance

to combustibles for hot water pipes.

Pipe the discharge of the relief valve (full size)

to a drain or in a manner to prevent injury in the event

of pressure relief. Install an air purger, an air vent,

a diaphragm-type expansion tank, and a hydronic

flow check in the system supply loop. Minimum fill

pressure must be 12 psig (82.7 kPa). Install shutoff

valves where required by code.

Suggested piping diagrams are shown in Figures

4, 5, 6, 7 and 8. These diagrams are meant only as a

guide. Components required by local codes must be

properly installed.

Note the recommended location of the

temperature sensor on the diagrams; you must provide

a location for the additional sensor shipped with the

Pennant. This sensor may be strapped onto pipe from

1" to 4" diameter, or inserted into an immersion well.

Distance from Gas Meter or Last Stage Regulator

Model and

Gas Type

0-100'

0-31 m

100-200'

31-61m

200-300'

61-91m

200 natural

11⁄4"

3.2 cm

11⁄4"

3.2 cm

11⁄4"

3.2 cm

200 propane

1"

2.5 cm

1"

2.5 cm

11⁄4"

3.2 cm

300 natural

11⁄4"

3.2 cm

11⁄2"

4.0 cm

11⁄2"

4.0 cm

300 propane

1

2.5 cm

11⁄4"

3.2 cm

11⁄4"

3.2 cm

400 natural

11⁄4"

3.2 cm

11⁄2"

4.0 cm

2"

5.0 cm

400 propane

11⁄4"

3.2 cm

11⁄4"

3.2 cm

11⁄2"

4.0 cm

Notes:

1. These figures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing

.

Table 7. Gas Piping Size.

Advertising
This manual is related to the following products: