6613_OMU_2+2S_URT_V1_00 Firmware Description Document

Rev. 1.1

25

Table 3: Outlet 2 MPU Outputs

Output

Location

(hex)

LSB

Comment

Example

Delta

Temperature

60

0.1 °C

Temperature difference from 22° C.

If external temperature is 32 °C

)60?<CR>

Returns:

+10.0

Line

Frequency

61

0.01 Hz

Line Frequency

If the line frequency is 60 Hz:

)61?<CR>

Returns:

+60.00

Alarm Status

62

Definition for Status Register

Bit 0: Minimum Temperature Alarm.
Bit 1: Maximum Temperature Alarm.
Bit 2: Minimum Frequency Alarm.
Bit 3: Maximum Frequency Alarm.
Bit 4: SAG Voltage Alarm.
Bit 5: MINVA

under minimum

voltage on VA input.
Bit 6: MAXVA

over maximum

voltage on VA input.
Bit 7: Reserved.
Bit 8: MAXIA WB

maximum WB

current exceeded on outlet 1.
Bit 9: Reserved.
Bit 10: Reserved.
Bit 11: PFA negative WB

Power

Factor Negative Threshold Alarm.
Only available if )F2 bit 2 is 1.
Bit 12: PFA positive WB

Power

Factor Positive Threshold Alarm for
outlet 1.
Bit 13: Reserved.
Bit 14: MAXIB_WB

maximum

wideband current exceeded on
Outlet 2.
Bit 15: Reserved.
Bit 16: Reserved.
Bit 17: PFB_WB negative

Wideband Power Factor Negative
Threshold Alarm for Outlet 2. Only
available if )F2 bit 2 is 1.
Bit 18: PFB_WB positive

Wideband Power Factor Positive
Threshold Alarm for Outlet 2.
Bit 19: MAXIT_WB

maximum total

wideband current exceeded on both
Outlet 1 and Outlet 2.
Bit 20: Reserved.
Bit 21: CREEP A Alert – Creep Alert
on Outlet 1.
Bit 22: CREEP B Alert – Creep Alert
on Outlet 2.
Bit 23: Line/Neutral Reversal
detected. Only available in non-
isolated mode (CESTATE, Bit 2=1)
Bit 24 –31: Reserved.

Alarms become “1” when

thresholds exceeded.

Note: Additional Status Alert is

Located at addr 0xBD (see

Table 4

)

Note: When AC voltage input is less

than or equal to 10 V

RMS

,

Only MINVA alarm is active.

All measurements are forced
to 0 except power factor,
which is forced to 1.

Note: The frequency measurement

is forced to 0 as long as the SAG

voltage alarm is active.