E8-ef 35 – Maxim Integrated 6613_OMU_2+2S_URT_V100 User Manual

Page 35

Advertising
background image

UG_6613_ 060

6613_OMU_2+2S_URT_V1_00 Firmware Description Document

Rev. 1.1

35

MPU

Parameter

Location

(hex)

LSB

Default

Comment

Example

Unused

DA - DB

PFA_ Neg

Threshold

DC

-0.700

Power Factor Negative Threshold.

A less negative power factor than

this threshold will set an alarm (bit

11 of the Alarm Status Register).

Only available if )F2 bit 2 is set to

1.

If the negative power factor
threshold is to be changed

from the default to -0.6 then

set as follows:

)DC=-0.600<CR>

PFA_ Pos
Threshold

DD

+0.700

Power Factor Positive Threshold.

A positive power factor less than

this threshold will set an alarm (bit

12 of the Alarm Status Register).

If the positive power factor

threshold is to be changed

from the default to +0.6

then set as follows:

)DD=+0.600<CR>

Unused

DE - DF

Unused

Unused

E0 - E5

Unused

Alarm

Mask_Reg

E6

00201FFF

Alarm mask for bits in the Alarm

Status register. A “0” masks the

alarm from the register bit.

If bits 0 and 1 are to be

masked then set as follows:

>)E6=00801FFC

Alarm

Mask_DIO

E7

00201FFF

Alarm mask for an alarm pin

(DIO20). A “0” masks the alarm

from DIO20

Alarm mask for an alarm

pin (DIO20). A “0” masks

the alarm from DIO20

RESERVED

E8-EF

RESERVED

Control Relay

F0

0

Bit 1 (Relay for Outlet 2)

0 = DIO19 = 0

1 = DIO19 =1

Bit 0 (Relay for Outlet 1)

0 = DIO7 = 0
1 = DIO7 = 1

Note: AC[1] = 1 inverts the bits

above.

Control Relay

Min/Max

Control

F1

0

BIT1 – 1 Start/Stop MIN/MAX
recording.
1 = Start
0 = Stop
BIT0 – 1 Reset MIN/MAX
registers before recording. Bit
autoclears.


Reset & Start MIN/MAX

recording.

)F1=3<CR>

Stop MIN/MAX recording

)AC=00<CR>

Clear Control

and Power

Factor Polarity

F2

0

Clear Control and Power Factor
Polarity Register:
Bit 2 – Power Factor Polarity
0 = Power Factor is
positive only. Negative alarm
thresholds and alarms are not
enabled.
1 = Power factor can be
positive or negative.

Bit1 – Clears Counts
Bit 0 – Clears Accumulators.

Advertising