6613_OMU_2+2S_URT_V1_00 Firmware Description Document

UG_6613_060

34

Rev. 1.1

MPU

Parameter

Location

(hex)

LSB

Default

Comment

Example

Frequency

Minimum

Threshold

D2

0.01Hz

+59.00

Minimum Frequency Alarm

Threshold. A frequency below

this threshold will set the alarm

(bit 2 of the Alarm Status

Register).

If the minimum frequency

threshold is to be changed

to 59.50 Hz then enter the

following:

>)D2=+59.50

Frequency

Maximum

Threshold

D3

0.01Hz

+61.00

Maximum Frequency Alarm

Threshold. A frequency above
this threshold will set the alarm

(bit 3 of the Alarm Status

Register).

If the maximum frequency

threshold is to be changed

to 60.50 Hz then enter the

following:

>)D2=+60.50

SAG Voltage

Alarm

Threshold

D4

mVpk

+80.0

Sets an alarm (bit 4 of the Alarm

Status Register) if voltage drops

below the SAG threshold.

Min Voltage

Alarm

Threshold

D5

mVrms

+100.000

Minimum voltage level selected to

flag user (bit 5 of the Alarm Status

Register).

To change the minimum

voltage threshold from the

40 Volt default to 80 Volts:

)D5=+80.000<CR>

Peak Voltage

Alarm

Threshold

D6

mVrms

+140.000

Peak voltage setting that user

wishes to flag (bit 6 of the Alarm

Status Register).

To change the peak voltage

threshold from the default

407.3 Volts to 280 Volts:

)D6=+280.000<CR>

Unused

D7-D8

Peak IA

Alarm

Threshold

D9

mArms

+15.000

Maximum Current measured on

the IA channel above which a flag

must set (bit 8 of the Alarm Status

Register).

If the peak current

threshold is to be changed

from the default value of 15

Amps to 30 Amps then set

as follows:

)D9=+30.000<CR>