Switch – Eclipse Combustion 6500 User Manual

Page 13

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

13

S2 DIP Switches

The S2 DIP switches permit programming of timing and sequence
functions of the Bi-Flame.

Note:
The S2 DIP switch settings at left are for illustrative purposes
only; the actual settings of any of these switches will be
determined by your system conditions.

SW1: Recycling mode selection (On=Recycling; Off=Non-recycling)

SW2: Pilot selection (On = Intermittent, where pilot remains on during
burner cycle; Off = Interrupted, where pilot valve closes after main
burner is established).

SW3: Trial-for-ignition (TFI) range selection; used with SW7 of the S4
DIP switch. See the table at left for proper selection.

SW4 through 8: Purge time selection; switch in off position selects
indicated purge time. Selected purge times are additive. See
illustration at left for exact times.

S4 DIP Switches

SW1: Fan operation on flame failure (on = fan turns off; off = fan stays
on).

SW5: Leak test time (on=110 seconds; off=40 seconds).

SW7: Trial-for-ignition (TFI) range selection; used with SW3 of the S2
DIP switches. See the table at left for proper selection.

SW8: Purge mode; (on = modulation, off = process).

S6 DIP Switches

The S6 DIP switches are factory set for two burners. DO NOT
CHANGE. Any other setting will result in an “UNMATCH#” fault
condition.

DIP

SWITCH

SETTINGS

SW6: Off, Not used.

SW7: Off, Not used.

SW8: Frequency Selection; (On = 50Hz, Off = 60 Hz)

8
7
6
5
4
3
2
1

8
7
6
5
4
3
2
1

8
7
6
5
4
3
2
1

50/60Hz


MOD/PROC

TFI

LEAK 110/40



BLOWER

Number

of

PAF

P

U

R

G

E

X4

120/8

60/4
30/2
15/1

TFI

PILOT IMIT/IRPT

RECYCLE

S6

S4

S2

8
7
6
5
4

X4

120 sec.

60 sec.
30 sec.
15 sec.

ON

OFF

Time

Not

Added

S2 Modulation Purge Time, S4 - 8 = ON

8
7
6
5
4

X4

8 min.
4 min.
2 min.
1 min.

ON

OFF

Time

Not

Added

S2 Process Purge Time, S4 - 8 = OFF

ON/OFF

DIP Switch Functions

Trial-for-Ignition (TFI) Settings

If the

TFI

needed is:

5 seconds

10 seconds

15 seconds

THEN

SW3 of S2

DIP switch

must be

turned:

Off

Off

On

AND

SW7 of S4

DIP Switch

must be

turned:

Off

On

Off or On

S2

S2

Advertising