Specifications, Parameter description – Eclipse Combustion 6500 User Manual

Page 8

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

8

I

NTRODUCTION

Specifications

This section gives a detailed overview of Bi-Flame specifications and
dimensions.

2

Specifications

Parameter

Description

Supply

•120 VAC (+10%, -15%), 50/60 Hz standard.

Internal

power

consumption:

24VA

Temperature Ranges

Unit

Model Nos.

Temperature Range

Bi-Flame

6500

-40˚

to

+60˚C

(-40˚

to

+140˚F)

90˚ U.V. Scanner

5600-90A

-20˚ to +60˚C (0˚ to 140˚F)

U.V. Scanner

5600-91

-40˚ to +125˚C (-40˚ to +257˚F)

NEMA4 UV Scanner

5600-91N4

-20˚ to +125˚C (0˚ to 257˚F)

Self-Check

U.V.

5602-91

-40˚

to

+60˚C

(-40˚

to

+140˚F)

Remote

Display

6000D

to

50˚C

(32˚

to

122˚F)

Flame Failure Response

• 3 seconds ±0.5 seconds.

TFI/Pilot Interrupt

• 5, 10 or 15 seconds selectable.

Purge Time

• Modulating: selectable from 0-225 seconds in 15 second increments,

or 0-15 minutes in 1 minute increments

• Process: selectable from 0-15 minutes in 1 minute increments,

or 0-60 minutes in 4 minute increments.

Contact Ratings @ 120 VAC

Function

Affected Terminals

Inductive Load Resistive Load

(maximum total connected

Output Relay

J2-4 through J2-8

1/3 HP

10 amps

load not to exceed 15 amps)

Output Relay

J2-3

1/2 HP

15 amps

Modulation

J3-1 through J3-4

1/3 HP

10 amps

Approvals

• UL Recognized; File MP1537 (category MCCZ2)

• FM Approved; J.I. 2Y3A5.AF (class 7610)

• CSA Certified; File 007989-0-000 (class 2632-01, 2642-01)

Shipping Weight

• 2.7 kilograms (6 lbs.)