Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

36

Table 10.1

Bi-Flame Operating Sequence

POWER ON

Was internal safe start check successful?

EXTERNAL INTERLOCK CHECKS

Is flame signal present?

BURNER START-UP

(see next page)

YES

NO

YES

NO

YES

NO

YES

NO

Various lockout messages

Fan output is energized; modu-
lator is sent to low fire.

YES

NO

Holds until answer is yes.

Is proof of closure circuit closed?

Is voltage present at air flow switch?

Is voltage present at interlock switch?

ERROR MESSAGE

MAIN VALVE FAIL
LKOUT XXXX:XX:XX

ERROR MESSAGE

LIMITS OPEN
TIME = XXXX:XX:XX

NORMAL MESSAGE

FAN ENERGIZED

ERROR MESSAGE #1

UNSAFE FLAME ON

NORMAL MESSAGE

VERSION VX.X
CHECKSUM = XXXX

Fan and Alarm energized.

If signal is eliminated within 30
seconds, sequence continues. If
not, then . . .

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE FLAME ON
LKOUT XXXX:XX:XX

ERROR MESSAGE #1

UNSAFE AIR SHORT

Fan and Alarm energized.

If switch is not opened within
30 seconds and the limit input is
present....

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE AIR SHORT
LKOUT XXXX:XX:XX

Fan and Alarm energized.

Is voltage present at AUX inputs ?

YES

Countdown of XX based on DIP
switch

NORMAL MESSAGE

VALVE LEAKAGE
UNDER TEST XX

Is voltage present at VDK input
before time out?

YES

NO

#X is 1, 2, 3, or 4 to show
absent input

ERROR MESSAGE

AUX. LIM. # X FAIL
LKOUT XXXX:XX:XX

NO

Fan and alarm energized.

ERROR MESSAGE

VALVE LEAK FAIL
LKOUT XXXX:XX:XX

NORMAL MESSAGE

SAFE START OK
VX.X CS=XXXX