Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

41

Table 10.2

Remote Display Diagnostic Messages (continued)

MESSAGE

TYPE

EXPLANATION

Lockout

Main flame was not established during the main burner trial for ignition.

Lockout

Main valve has been energized and main flame proven during trial
for ignition.

Status

Pilot valve (strip J2, terminal 5) is de-energized and main flame is on.

Lockout

Main valve proof-of-closure is open before startup or after burner
shutdown.

Lockout

Pilot flame was not established during the pilot trial for ignition.

Status

Pilot flame is proven; transformer is de-energized; remaining
countdown for pilot trial for ignition is “XX”.

Status

Pilot valve and ignition transformer are energized; countdown for
pilot trial for ignition begins at “XX”.

Lockout

An external source of voltage is present on the ignition, pilot or
main output terminals.

Status

15 second post purge is started on burner shutdown; “XX” shows
countdown.

Lockout

DIP switch improperly set or changed during cycle.

Status

Modulating motor is sent to high fire; “XX” shows purge countdown.

Status

Part of the optional history log which records the total number of
operating cycles and the last lockout messages up to a maximum
of 10.

Lockout

Internal relay(s) fail initial check. Check ratings. If lockout still oc-
curs after overload is eliminated, replace control.

Status

Control has completed internal safe-start check.

Status

Combustion air switch is closed before start-up or after shut-
down; control holds start-up until switch re-opens; if interlocks
close before switch opens, alarm will energize in 30 seconds.

Lockout

Same conditions as above, except the interlocks closed for 30 sec-
onds before the switch re-opened, causing a lockout and the alarm.

MAIN # ( ) FAILED

MAIN FLAME ON

MAIN FLAME ON
PILOT OFF

MAIN VALVE FAIL
LKOUT XXXX:XX:XX

PILOT FLAME FAIL
LKOUT XXXX:XX:XX

PILOT ON

XX

PILOT TRIAL FOR
IGNITION

XX

PLT/MVL ENERGIZ.
XX:XX:XX LOCKOUT

POST PURGE

XX

PROGM SWITCH ERR
LKOUT XXXX:XX:XX

PURGE AT HIGH
FIRE XX

RECORD #X

RELAY FAIL
LKOUT XXXX:XX:XX

SAFE START OK

UNSAFE AIR SHORT

UNSAFE AIR SHORT
LKOUT XXXX:XX:XX