Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

40

MESSAGE

TYPE

EXPLANATION

Table 10.2

Remote Display Diagnostic Messages (Listed Alphabetically)

Lockout

Combustion air flow limit switch (strip J1, terminal 2) opened for
more than two seconds once initially proven.

Status

Combustion air flow limit switch (strip J1, terminal 2) opened;
control will recycle once if “recycle” DIP switch has been se-
lected.

Lockout

Combustion air flow limit switch (strip J1, terminal 2) did not
make within ten seconds of fan being energized.

Status

Combustion air flow limit switch (strip J1, terminal 2) closed
within ten seconds of fan being energized.

Status

Modulating motor is sent to automatic operation. Terminal 1 is
connected to terminal 2 on terminal strip J3.

Lockout

Auxiliary input #1 has lost its voltage during system operation,
causing a lockout at the indicated time.

Lockout

Auxiliary input #2 has lost its voltage during system operation,
causing a lockout at the indicated time.

Lockout

Auxiliary input #3 has lost its voltage during system operation,
causing a lockout at the indicated time.

Lockout

Auxiliary input #4 has lost its voltage during system operation,
causing a lockout at the indicated time.

Status

Blower motor (strip J2, terminal 3) is energized at the start of pre-purge.

Status

Main flame lost during automatic modulation; control will recycle
once if “recycle” has been selected.

Lockout

Main flame lost during operation in the automatic modulation
mode. Burner number (X) given of failed unit.

Status

Main flame of burner number (Y) is proven in the automatic modula-
tion mode; flame strength is XX.XV (volts DC). Elapsed time is
shown in hours:minutes:seconds.

Lockout

High damper or high purge rate switch did not make and hold for
high pre-purgee.

Lockout

Internal control failure; replace controller.

Status

The controller has completed its internal checks and is standing by
for the interlocks (strip J1, terminal 1) to close.

Lockout

Low fire switch (strip J1, terminal 4) is open just prior to pilot trial
for ignition.

AIR FAILURE
LKOUT XXXX:XX:XX

AIR FAILURE
RECYCLING

AIR NOT PROVEN
LKOUT XXXX:XX:XX

AIR PROVEN

AUTOMATIC
MODULATION

AUX.LIM.#1 FAIL
LKOUT XXXX:XX:XX

AUX.LIM.#2 FAIL
LKOUT XXXX:XX:XX

AUX.LIM.#3 FAIL
LKOUT XXXX:XX:XX

AUX.LIM.# 4 FAIL
LKOUT XXXX:XX:XX

FAN ENERGIZED

FLAME # ( ) FAIL
RECYCLING

FLAME # (X) FAILED
LKOUT XXXX:XX:XX

FLAME # (Y) XX.XV
TIME=XXXX:XX:XX

HI FIRE FAIL

INTERNAL FAULT

LIMITS OPEN
TIME=XXXX:XX:XX

LOW FIRE FAIL
LKOUT XXXX:XX:XX