Eclipse Combustion 6500 User Manual

Page 20

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

20

Air

This LED illuminates when the air switch is closed and power is
thereby applied to the air switch input. The Bi-Flame also checks this
input for an air switch short (see “Combustion Air Flow Check Ter-
minal” on page 14).

Purge

This LED illuminates whenever the combustion blower is energized,
including the purge period and the main burner period of the se-
quence. It blinks on and off while the purge is in process and remains
constant when the purge process is complete.

Burner On

This LED illuminates when the main gas valve is energized, permitting
gas flow to all the burners.

Fault

This LED illuminates when a system fault is detected (see “System
Faults” on page 21).

Alarm

This LED illuminates when an alarm condition causes a system lock-
out (see “System Lockout Conditions” on page 21).

Low Fire

This LED illuminates during the low fire period of the purge cycle.

High Fire

This LED illuminates during the high fire period of the purge cycle.

Scan

This push-button can be used to scroll the history log.

Enter

This push-button is used with the RESET button to enable the pilot
test mode.

Reset

This push-button resets the control. It is also used with the ENTER
button to enable the pilot test mode.

Advertising