Eclipse Combustion 6500 User Manual

Page 26

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

26

Figure 6.2

Wiring Diagram & Connections –Main Chassis

On/Off

Alarm

Fan Motor

Interlocks & Limits

Air Flow

120 VAC

POVC

15 A. Fuse

6

7

8

9

10

1

2

3

5

4

Low Fire

High Fire

6

7

8

1

2

3

5

4

MS

Aux. Input #41

Aux. Input #31

Aux. Input #21

Aux. Input #11

Leak Detect

Neutral

Main

Leak Detect

Pilot

Ignition

1

2

3

4

Flame Rod

Shield

Blue

5600-90A

or 5600-91

U.V. Scanner

Yellow

Main Gas Valve

Block Valve

Pilot Gas Valve

Neutral

J1

Terminals

J2

Terminals

J4

Terminals2

J5

Terminals2

Burner #1

1

2

3

4

Flame Rod

Shield

Yellow

Blue

Burner #2

6

5

4

3

1

2

RS 232

Rx

Tx

Remote

Reset

Pushbutton

(if required)

VDK/VLSD

J7

Terminals

When not used, must be tied into 120 VAC.

1

Using both sensors isn’t mandatory; you may use a flame rod, or a UV scanner, or both.

2

J1 (Input) Terminals

1 – Limits Input
2 – Air Switch Input
3 – POVC Switch Input
4 – Low Fire Switch Input
5 – High Fire Switch Input
6 – VDK/VLDS Input
7 – Aux. #11
8 – Aux. #21
9 – Aux. #31
10 – Aux. #41

J7 (Interface) Terminals

Auxiliary
Inputs

1 – Flame Rod
2 – Ground (Yellow)
3 – U.V. (Blue)
4 – Shield Connection

1 – U.V. (Blue)
2 – Ground (Yellow)
3 – Flame Rod
4 – Shield Connection

J2 (Output) Terminals

1 – Neutral
2 – 120 VAC
3 – Fan
4 – Main Gas Valve
5 – Pilot Gas Valve
6 – Ignition Transformer
7 – VDK/VLSD
8 – Alarm

Bi-Flame
Power Inputs

Outputs

J3 (Modulation) Terminals

1 – Common
2 – Auto
3 – Hi Fire
4 – Low Fire

Modulation
Motor
Connections
for High Fire &
Low Fire Start

J4 (Sensors/Burners 1 & 3) Terminals

2

Burner #1

J5 (Sensors/Burners 2 & 4) Terminals

2

Burner #2

6 – RS 232/RS 485 Interface
5 – RS 232/RS 485 Interface
4 – Reset
3 – Scan
2 – Enter
1 – Ground

5600-90A

or 5600-91

U.V. Scanner

GND (Return)

D

C

A

B

Signal (UV)

Neutral

120 VAC

5602-91

U.V.

Self-Check

Scanner

VDK/VLSD

Customer Supplied (if used)

1

2

3

4

Common

Auto

High Fire

Low Fire

J3

Terminals

P1-1

P1-2

P1-4

+

-

ACT004

Temperature

Controller

4 to 20 mA

Ignition Coil

Ignition Coil

Advertising