Burner start-up (continued), Table 10.1 bi-flame operating sequence (continued) – Eclipse Combustion 6500 User Manual

Page 38

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

38

Table 10.1

Bi-Flame Operating Sequence (continued)

BURNER START-UP (continued)

Is flame signal present ?

NO

Modulator sent to automatic 20
seconds after main valve is
energized.

Pilot will shut off 10 seconds
after main flame is energized.

Flame signal = XX.X Volts DC;
(X) = Number of burner being
monitored; the Bi-Flame will
scroll through each burner con-
tinuously during the burner-on
cycle.

YES

X = burner number.

ERROR MESSAGE

MAIN # (OX) FAILED

AUTOMATIC
MODULATION

NORMAL MESSAGE

NORMAL MESSAGE

FLAME #(OX) XX.XV
TIME = XXXX:XX:XX

IF Interrupted Pilot is selected

NORMAL MESSAGE

MAIN FLAME ON
PILOT OFF

NORMAL MESSAGE

MAIN FLAME ON

Advertising