Burner shutdown, Yes no – Eclipse Combustion 6500 User Manual

Page 39

Advertising
background image

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

39

Table 10.1

Bi-Flame Operating Sequence (continued)

BURNER SHUTDOWN

Shutdown is started by opening

the operating interlock circuit.

Is voltage present at interlocks?

YES

NO

Fuel valves de-energized; fan
energized for 15 seconds.

Is proof of closure circuit closed?

YES

NO

Is voltage present at air flow switch?

YES

NO

Fan and alarm energized.

Fan and Alarm energized.

ERROR MESSAGE

MAIN VALVE FAIL
LKOUT XXXX:XX:XX

NORMAL MESSAGE

LIMITS OPEN
TIME = XXXX:XX:XX

Fan is energized. If signal is elimi-
nated within 30 seconds, se-
quence continues. If not, then . .

ERROR MESSAGE #1

UNSAFE FLAME ON

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE FLAME ON
LKOUT XXXX:XX:XX

NORMAL MESSAGE

POST PURGE
XX

ERROR MESSAGE #1

UNSAFE AIR SHORT

YES

NO

Is flame signal present?

Alarm energized.

If switch is opened within 30
seconds, sequence continues. If
not, then . . .

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE AIR SHORT
LKOUT XXXX:XX:XX

Continued operation.

Countdown of XX based on DIP
switch

NORMAL MESSAGE

VALVE LEAKAGE
UNDER TEST XX

Is voltage present at VDK input
before time out?

YES

NO

Fan and alarm energized.

ERROR MESSAGE

VALVE LEAK FAIL
LKOUT XXXX:XX:XX