Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

37

Table 10.1

Bi-Flame Operating Sequence (continued)

BURNER START-UP

Is voltage present at air flow switch

within ten seconds?

Is flame signal present?

(see next page)

After “XX” equals zero (0)...

Spark energized until pilot flame
proven; pilot valve energized for
countdown of “XX” seconds
(“XX” equals selected trial for
ignition).

Is pilot flame signal present?

YES

NO

Is flame signal present?

YES

NO

X = burner number.

ERROR MESSAGE

PILOT # (0X) FAILED
LKOUT XXXX:XX:XX

ERROR MESSAGE

MAIN # (0X) FAILED
LKOUT XXXX:XX:XX

Countdown of “XX” seconds
as set by DIP switch.

NORMAL MESSAGE

PURGE AT HIGH
FIRE XX

Modulator sent to low fire.

NORMAL MESSAGE

WAIT FOR LO.FIRE
SWITCH XX:XX

NORMAL MESSAGE

PILOT ON
XX

NORMAL MESSAGE

MAIN FLAME ON

NORMAL MESSAGE

PILOT TRIAL FOR
IGNITION XX

YES

NO

YES

NO

Is voltage present

at low fire input?

ERROR MESSAGE

AIR NOT PROVEN
LKOUT XXXX:XX:XX

ERROR MESSAGE

LOW FIRE FAIL
LKOUT XXXX:XX:XX

NORMAL MESSAGE

AIR PROVEN

Modulator sent to high fire.

NORMAL MESSAGE

WAIT FOR HI. FIRE
SWITCH XX:XX

YES

NO

Is voltage present

at high fire input?

ERROR MESSAGE

HIGH FIRE FAIL
LKOUT XXXX:XX:XX

X = burner number.

Delay 5 seconds.

NORMAL MESSAGE

PILOT ON
IGNITION OFF