TROUBLESHOOTING

Basic Troubleshooting Guide

Checking For Proper LVS Operation

Inspection holes are provided at the rear of the rack in order to
verify whether the two rack power supply (LVS) units are working
properly. Each LVS has a green LED indicator which should be lit
when power is applied to the rack.

At rear of rack, ensure proper operation of LVS units by checking
LED status as follows:

Both LEDs lit: Status okay, both LVS units operating properly.

One LED lit: Status okay, but indicates that one LVS unit is not
working and should be replaced.

No LEDs lit: Failure situation, both LVS units need to be
replaced.

Symptom(s)

Solution(s)

No power to rack.
Phase indicators not lit.

1. Ensure Mains Cable Cam-Loks are connected to Inputs.
2. Turn on breaker at 400 Amp Disconnect.
3. Check for LVS failure (see below).

No power to connected devices or
convenience outlets.

1. Engage green Master Switch button.

Power to convenience outlets, but not
to connected fixtures (via Trunk Cable).

1. Switch breakers at front of Breaker Module(s) to ON position.
2. Ensure Trunk Cables are mated to matching Breakout Box.

No "clicking" sound when a Trunk
Cable is connected to Breaker Module.

1. Ensure Breakout Box rating matches Breaker Module rating

(120V or 208V) .

No control of connected fixtures.

1. Ensure DMX Universe(s) are correctly configured at Menu Display.

LVS
Inspection Holes

RACK REAR VIEW

Figure 4-1: LVS Inspection Holes