Reconfiguring components, About reconfiguring, Swapping a breaker module – PRG S400 User Manual 3.1 User Manual

Page 61

Advertising
background image

PRG SERIES 400

®

POWER AND DATA DISTRIBUTION SYSTEM USER MANUAL

55

RECONFIGURING COMPONENTS

About Reconfiguring

The rack and other system components are configurable depending on system requirements. For example, the rack
can contain various types and quantities of Breaker Modules such as 120V and/or 208V or additional auxiliary
equipment. The Front of House Breakout Module can be installed independently or in a rack unit itself.

WARNING:

In any configuration, the rack should

never

have any unfilled gaps. Special 1U, 2U and 3U safety

covers are available to cover any gaps in the rack tower due to custom configurations.

Swapping a Breaker Module

The Breaker Modules are hot-swappable, allowing the components to be changed quickly even while the system is
under operation. In the event a module needs to be swapped or the rack needs to be reconfigured, use the following
procedure.

WARNING:

Every space in the rack

must

be filled with either a module or a rack spacer cover

at all times

.

For spacer cover part numbers, refer to

"Accessories"

on page 12.

Tools:

#2 Phillips Screwdriver

To replace a Breaker Module:

Step

1. At rear of Breaker Module, disconnect any trunk cables.

Step

2. At front of module, disconnect any data cables.

Step

3. Remove four screws securing module. Using handles, pull module straight out of rack.

Step

4. Install new module and reconnect cabling.

Figure 4-4: Replacing a Breaker Module

Screw (4)

Breaker Module

15A 208V MODEL SHOWN

Rack Components May Vary

Advertising