PROHEAT G-I PCM SERVICE MANUAL

4-3

START Diagnostic Code 1

Indicates that the G-I PCM Flame Sensor did not detect a flame or the flame

was too weak to be detected during the FULL 30 second ignition period.

Troubleshoot the Start diagnostic code based on the following symptoms:

1.

Fuel System. Go to page 4-4 to page 4-17, Steps 1 through 7.

a) There is no fuel, fuel odor or atomized fuel coming from the exhaust pipe.

b) There is no hot exhaust coming from the exhaust pipe.

2.

Ignition System. Go to page 4-20.

a) There is raw fuel and/or atomized fuel and a raw fuel odor coming

from the exhaust pipe.

b) There is no hot exhaust coming from the exhaust pipe.

3.

G-I PCM (PROHEAT Control Module) Flame Sensor circuit. Go to page 4-22.

a) There is a flame and the combustion sounds good, the PROHEAT

appears to be operating normally.

b) No smoke, raw fuel odor or atomized fuel is coming from the exhaust pipe.

4.

Motor and/or G-I PCM fault. Go to page 4-24.

a) The Motor is NOT running. Ignition and Coolant Pump are operating.

b) No smoke, raw fuel odor or atomized fuel coming from the exhaust pipe.

4.1.2

(1 Flash)

The Motor and Coolant Pump start first, followed by the ignition spark, and

then Fuel Shut-off Valve opens. The Ignition Module sparks for 30 seconds

during which time the flame sensor must detect a proper flame. At the end of

the Ignition cycle the Flame Sensor checks the flame:

• In this error example, the PROHEAT does not detect proper flame and the

PROHEAT enters Error Detection – Cool Down (Purge).

3. Ignition

The PROHEAT always restarts after one error detection. After the 3 minute

Cool Down (Purge), the PROHEAT will go through Precheck, Ignition and the

Error Detection – Cool Down (Purge) cycle one more time.

5. Steps 2 to 4

are Repeated

After two consecutive Code 1 errors, the PROHEAT goes into a Fault Shut

Down state. No further start attempts will be made.

The ON/OFF switch lamp, timer lamp or OEM indicator light will continue to

flash once, pause and repeat.

NOTE: In order to restart the heater, turn the switch “OFF” and back “ON”.

6. Fault Shut

Down

The flame sensor did not “see” a flame by 30 seconds after entering ignition:

the fuel solenoid closes and the Motor and Coolant Pump continue to

operate for three minutes.

Code 01 will flash on the ON/OFF switch lamp, timer lamp or OEM indicator

(installation options). There will be one flash, pause and then one flash

repeating on the ON/OFF switch lamp, timer lamp or OEM indicator. After 3

minutes, the Motor and Coolant Pump stops and the PROHEAT attempts to

start again.

4. Error

Detection –

Cool Down

(Purge)