12

5.5. FS-7000AT Attenuator Control Panel

The FS-7000AT is used in conjunction with FS-7000 Series Voice Evacuation Systems to control 4-wire
system attenuators. Up to 10 zones can be attenuator-controlled. When general urgency or emergency
broadcasts are made, the FS-7000AT provides 24 V DC power to allow such broadcasts to bypass the
attenuators. The output status of each line can be monitored by the indicators on the front panel.

[Front]

2

3

1

1. Power Indicator

Lights when power is supplied and the FS-7000AT
is ready for operation.

2. Attenuator Line Indicators

Light when 24 V DC for bypassing the attenuators
are being supplied, and extinguish when the
overcurrent protection circuit is triggered due to
line shorts or other failures, or when the power
supply is cut off.

3. Broadcast Zone Fill-In Space

Write the names of the corresponding broadcast
zones in this space.

5.4. FS-7000PS DC Power Supply Panel

The FS-7000PS supplies 24 V DC power to each component used in FS-7000 Series Voice Evacuation
Systems. Connecting the DS-029B provides a power supply for emergency broadcasts even during power
failures.

[Front]

1

2

3

1. AC Power Switch

AC power is turned on and off with each press of
this switch.

2. AC Power Indicator

Lights when AC power is supplied and the FS-
7000PS is ready for operation on AC power.

3. DC Power Indicator

Lights when DC power is supplied and the FS-
7000PS is ready for operation on DC power.