Press the Evacuation announcement button on the FS-7000EV.
The Evacuation announcement indicator will extinguish and the evacuation announcement will be stopped.
To resume the evacuation announcement, press the Evacuation announcement button again.

Tip
If an additional fire instruction signal is received from the automatic fire alarm system:
• The appropriate broadcast areas are selected and the Zone indicators illuminate.
• If no evacuation announcement is already in progress, then the additional instruction signal activates

evacuation announcements automatically.

After the automatic fire alarm system has been reset, press the Emergency reset button on the FS-
7000EV.
The Fire indicator and Evacuation announcement indicator will extinguish, and original general-purpose
broadcasts will resume automatically.

Tip
Priority broadcasts from the FS-7000CP unit and 1-channel BGM broadcasts will not resume automatically.

Activate the false alarm announcement by pressing the False alarm announcement button on the FS-
7000EV.
The False alarm announcement indicator will illuminate and the false alarm announcement will be sent.

Then, after resetting the automatic fire alarm system, press the Emergency reset button on the FS-
7000EV.
The Fire indicator will extinguish, and original general-purpose broadcasts will resume.

Tip
Priority broadcasts from the FS-7000CP unit and 1-channel BGM broadcasts will not resume automatically.

Making false alarm announcements

Terminating emergency announcements once a fire has been extinguished