5. NOMENCLATURE AND FUNCTIONS

5.1. FS-7000CP Control Panel

The FS-7000CP is a standard operation panel for the FS-7000 Series Voice Evacuation Systems.
It is designed to be used in conjunction with the FS-7000JP panel, and enables individual paging calls to up to
10 zones plus all-zone calls.
The number of zones can be expanded to up to 200 zones in 10-zone units by connecting the FS-7010CP
expansion panel. Further, connection of both the FS-7000GM panel and the FS-7010CP panel permits
creation of up to 20 broadcast zone groups.
The FS-7000CP is equipped with a built-in pre-amplifier function and chime unit (ascending 4-note tone).
Audio output can be set to either a 2-channel output of background music (BGM) and priority broadcast or a 1-
channel output of mixed BGM and priority broadcast.

[Front]

2

3

1

7

9

10

11 12 13

6

14

8

5

4

Inside of the front cover

1. Power Indicator

Lights when power is supplied and the FS-
7000CP is ready for operation.

2. CP Microphone

Make announcements while holding down the
Talk Switch (3). The microphone can be used only
while the FS-7000CP panel is in use or
emergency broadcasts are in progress.

3. Talk Switch

Hold down this switch to make announcements
using the microphone.

4. Volume Controls

Adjust the sound volume for each audio input.
Turning the control clockwise increases the
volume, while turning it counterclockwise
decreases the volume.
Controls are arranged from left to right as follows:

• EV
Adjusts the volume of the EV Audio Input on the
rear panel.
• TIMER
Adjusts the volume of the Timer Input on the rear
panel.
• PAGING
Adjusts the volume of the Paging Input on the rear
panel.
• RM MIC
Adjusts the volume of the RF Audio Input on the
rear panel.
• CP MIC
Adjusts the volume of the CP Microphone (2).
• CHIME
Adjust the volume of the built-in 4-tone chime.
• BGM 1 – 4
Adjusts the volume of BGM Inputs 1 – 4 on the
rear panel.