Toa FS-7000 SERIES Manual User Manual

Page 13

Advertising
background image

13

5.6. FS-7000EV Voice Evacuation Panel

The FS-7000EV is an emergency broadcast operation panel for FS-7000 Series Voice Evacuation Systems.
This panel is not required if the system is to be used solely for general-purpose public address applications. It
is possible to start and reset emergency broadcasts through manual operation. The FS-7000EV has a built-in
voice alarm device that can make both evacuation and false alarm announcements. Not only are evacuation
announcements automatically broadcast when the system receives a fire instruction signal from the connected
automatic fire alarm system, they can also be initiated using the Evacuation Announcement button on the front
panel. False alarm announcements can be initiated using the False Alarm Announcement button on the front
panel. Evacuation and false alarm announcement messages can also be recorded using the appropriate
buttons on the front of the panel, in which case the recorded message can be confirmed by listening with
headphones.

[Front]

2

3

4

7 8

9

10

11 12 13

1

6

5

1. Power Indicator

Lights when power is supplied and the FS-
7000EV is ready for operation.

2. Emergency Reset Button

When it is confirmed that a fire has been
extinguished or other emergency situations have
returned to normal, press this button to terminate
emergency broadcasts after resetting the
connected automatic fire alarm system.

3. Fire Indicator

Indicates that an emergency broadcast is in
progress. This indicator lights when a fire
detection signal is transmitted from the automatic
fire alarm system or when the Emergency
Activation button (4) is pressed.

4. Emergency Activation Button

Press this button to manually initiate emergency
broadcasts after the occurrence of fire has been
confirmed.

5. Mode Selector Switch

Selects the operation mode of the FS-7000EV unit
to be used as a sound source for evacuation and
false alarm announcements. Set the mode to
"NORMAL" in general use. No voice alarm is
output when the mode is set to "MONITOR" or
"RECORD."
Functions of the 3 switch positions are as follows:
NORMAL: Select this mode in general use. Voice

alarms are provided at the time of
emergency broadcast.

MONITOR: Allows the operator to listen to

messages recorded on a sound
source.

RECORD: Records evacuation and false alarm

announcements on a sound source.

(Default: NORMAL)

6. Evacuation Announcement Indicator

Lights or flashes when an evacuation
announcement is played back or recorded.

7. Evacuation Announcement Button

Press this button to play back or record
evacuation announcements.

8. False Alarm Announcement Indicator

Lights or flashes when a false alarm
announcement is played back or recorded.

9. False Alarm Announcement Button

Press this button to play back or record false
alarm announcements.

10. Input Sensitivity Setting Switch

Sets the input sensitivity of Recording Input (11).
Select the sensitivity depending on the type of
connected component.
(Default: –20 dBV)

11. Recording Input Terminal

Used for recording voice alarm messages.
(–60 dBV/2.2 kΩ or –20 dBV/10 kΩ selectable,
unbalanced, mini-jack)

12. Headphone Terminal

Connect headphones to this terminal to listen to
recorded messages for confirmation. Recorded
contents are output regardless of the settings of
the Mode Selector switch.
(0 dBV, 100 Ω, unbalanced, mini-jack)

13. Headphone Volume Control

Adjusts the volume of headphones.