TriangleTube Prestige Excellence Part 1 User Manual

Page 10

Advertising
background image

Pre-Installation Items

3

SECTION I - Pre-Installation Items

Code Compliance

This product must be installed in accordance to
the following:

-

All applicable local, state, national and
provincial codes, ordinances, regula-
tions and laws.

-

For installations in Massachusetts -
code requires the boiler to be installed
by a licensed plumber or gas fitter, and
if antifreeze is utilized, the installation
of a reduced pressure backflow preven-
ter device is required in the boiler’s cold
water fill or make up water supply line.

-

For installation in Massachusetts

All direct vented appliances must com-
ply with the guidelines as outlined on
page 11.

- The National Fuel Gas Code NFPA54/

ANSI Z 223.1 - Latest edition.

-

National Electric Code ANSI/NFPA 70.

- For installations in Canada -“Installation

Code for Gas Burning Equipment”
CGA/B149.1 or B149.2 Canadian
Electrical Code Part 1 CSA C22.1.

-

Standards for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1, when required.

The PRESTIGE Excellence boiler gas
manifold and gas controls meet the safe
lighting and other performance require-
ments as specified in ANSI Z21.13 latest
edition.

Determining Product Location

Before locating the PRESTIGE Excellence
check for convenient locations to:

-

Heating system piping

-

Venting

-

Gas supply piping

-

Electrical service

Ensure the boiler location allows the combus-
tion air/vent piping to be routed directly through
the building and terminate properly outside with
a minimum amount of length and bends.

Ensure the area chosen for the installation of the
PRESTIGE Excellence is free of any com-
bustible materials, gasoline and other flamma-
ble liquids.

Failure to remove or maintain the area
free of combustible materials, gasoline
and other flammable liquids or vapors
can result in severe personal injury,
death or substantial property damage.

Ensure the PRESTIGE Excellence and its con-
trols are protected from dripping or spraying
water during normal operation or service.

The PRESTIGE Excellence should be
installed in a location so that any water leaking
from the boiler or piping connections or relief
valve will not cause damage to the area sur-
rounding the unit or any lower floors in the
structure.

Boiler Replacement

If the PRESTIGE Excellence is replacing an
existing boiler, the following items should be
checked and corrected prior to installation:

-

Boiler piping leaks and corrosion.

- Improper location and sizing of the

expansion tank on the boiler heating
loop.

-

If applicable, level and quality of freeze
protection within the boiler system.

WARNING

NOTICE

Advertising