NATURAL GAS

Pipe Sizing - Natural Gas

Refer to Table 1 for Schedule 40 metallic pipe
length and diameter requirements for natural
gas, based on rated PRESTIGE Excellence
input (divide by 1,000 to obtain cubic feet per
hour).

-

Table 1 is based on Natural Gas with a spe-
cific gravity of 0.60 and a pressure drop
through the gas piping of 0.30”w.c..

- For additional gas piping sizing informa-

tion, refer to ANSI Z223.1. For Canadian
installations refer to B149.1 or B149.2.

Natural Gas Supply Pressure Requirements

1. Pressure required at the gas valve inlet

supply pressure port:

-

Maximum 13”w.c. at flow or no flow
conditions to the burner.

-

Minimum 5”w.c. during flow conditions
to the burner. Must be verified during
start up and with all other gas appliances
operating within the building.

2. Install 100% lockup gas pressure regulator

in the gas supply line if inlet pressure can
exceed 13”w.c at any time. Adjust the lock-
up pressure regulator for 13”w.c maximum.

DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve
is factory-set for the correct outlet pres-
sure. This setting is suitable for natural
gas and propane and requires no field
adjustment. Attempts by the installer to
adjust or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death or substantial property
damage.

WARNING

Table 1: Gas Piping Sizing - Natural Gas

Gas Piping