TO TEMPORARILY PLACE THE BURN-
ER INTO LOW FIRE TEST MODE:
press
the MODE button until “

StbY

” is displayed.

Then press and hold both the MODE and “-”
button simultaneously until the first digit flash-
es “L”.

TO DEACTIVATE THE HIGH OR LOW
FIRE TEST MODE:
Press and hold the “+”
and “-” button simultaneously to deactivate the
high or low fire test mode. While in the

StbY

” mode:

If the “+” button is held in the CH sys-
tem (parameter 3) will be turned OFF
and the display will show

cOFF

.

Press and hold the “+” button to turn the
CH system back ON, the display will
show “c” followed by CH set point tem-
perature (parameter 4) or CH target
temperature. If the “-” button is held in
while in the

StbY

mode domestic

system (parameter 2) will be turned OFF
and the display will show

dOFF

.

Press and hold “-” button to turn the
domestic system back ON, the display
will show “d” followed by domestic set
point temperature (parameter 1)

NOTICE

STANDBY, no demand for heat

Fan prepurge or post purge cycle

Ignition sequence

Burner ON for space heating (CH)

Burner ON for domestic hot water (DHW)

Pre-check for air flow prior to prepurge cycle

Burner OFF due to reaching temperature setpoint

Domestic hot water (DHW) post pump cycle

Space Heating (CH) post pump cycle

Burner blocked:

Supply temperature too high (202 F) . Burner

will remain OFF until temperature drops

below 200 F

Return temperature too high (202 F). Burner

will remain OFF until temperature drops

below 200 F

Return temperature is higher than

supply temperature. Burner will remain OFF

until corrected.
Supply temperature increased too quickly.

Burner will remain OFF for a 10 minute period.

Burner will recycle, increasing waiting period 1

minute for a max. 15 minutes

Factory supplied LWCO device or

external limit (terminals 15 & 16) is OPEN.

Burner off for 150 seconds, auto reset.

0
1

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

1

8

0

2
3
4
5
6
7
8
9

1

8

b

1

9

b

2

4

b

2

5

b

2

6

b

2

Display

Boiler function

No blower signal
Blower signal present with no demand, Burner

will remain OFF until condition terminates

Temperature difference between the supply and

return is more than 72 F. Burner will remain OFF

for 150 seconds. Burner will recycle increasing

wating period 1 minute for a max. 20 cycle.

Flue temperature sensor is short-circuited.

Burner OFF until corrected

Flue temperature senor is “open” Burner OFF

until corrected.

Flue temperature greater than 240 F but less

than 250 F. Burner off for 150 seconds

Wait for the blower to start

8

b

2

2

9

b

3

0

b

35

b

4

0

b

Indirect water heater temperature sensor is

short-circuited. Burner OFF until corrected.

Indirect water heater temperature sensor is

“open” or disconnected. Burner OFF until

corrected.

3

3

b

38

b

5

2

b

6

5

b

Power frequency deviation

1

1 6

b

Flame current signal lost

1

8

b

1

Standby Mode Display

Test function: Burner on, high fire mode

Test function: Burner on, low fire mode

180
180

H
L

Display

Boiler function

Start-Up Procedures

43