TriangleTube Prestige Excellence Part 1 User Manual

Page 35

Advertising
background image

SECTION VII - Internal Wiring

ELECTRICAL SHOCK HAZARD. For
your safety, disconnect electrical power
supply to the unit before servicing or
making any electrical connections to
avoid possible electric shock hazard.
Failure to do so can cause severe person-
al injury or death.

Prior to servicing, label all wires prior to
disconnection. Wiring errors can cause
improper and dangerous operation.
Verify proper wiring and operation after
servicing.

General Requirements

-

Wiring must be N.E.C Class 1.

-

If original wiring as supplied with the unit
must be replaced, use only Type T 90ºC
(190ºF) wire or equivalent as a minimum.

-

The PRESTIGE Excellence must be elec-
trically grounded as required by National
Electrical Code ANSI/NFPA 70 - latest edi-
tion and / or the Canadian Electrical Code
Part 1, CSA C22.1, Electrical Code.

Control Module Circulator AMP Ratings

-

AMP draw of the CH circulator not to
exceed 2 amps

Wiring Tool Instructions

1. Locate the wiring tool on the PRESTIGE

Excellence just below the MCBA control in
a plastic bag.

2. Locate the terminal blocks on the PRES-

TIGE Excellence below the MCBA con-
trol.

The 120V Terminals are located on the
left set of Terminal Blocks. The 24V
Terminals are located on the right set of
terminal blocks.

3. Carefully pull down on the lower half of

the terminal block to remove.

4. Hook the wiring tool into the desired slot of

the terminal block as shown in Fig.19.

5. Push wiring tool in towards the terminal

block and insert wire in slot at bottom of
terminal block.

6. Repeat steps 4 & 5 until all wiring is com-

plete.

7. Re-connect the lower half of the terminal

block to the upper half.

8. Place the wiring tool back into the plastic

bag or leave tool hooked to a slot on the
24V terminal block.

When

wiring

the

PRESTIGE

Excellence allow additional length of
wire for the access panel to swing open
during servicing.

WARNING

NOTICE

CAUTION

BEST PRACTICE

Terminal Block

Wiring Tool

Fig. 19: Using the wiring tool on the

terminal blocks

Internal Wiring

28