Venting system must be sealed gas-tight
to prevent flue gas spillage and potential
carbon monoxide emissions, which will
result in severe personal injury or death.

c

Check Gas Piping

Check around the unit for gas odor fol-
lowing the procedure outlined in this
manual on Page 36.

If any gas leaks are found or suspected,
shut the unit down immediately. Use a
gas detection device or bubble test to
locate the source of the gas leak and
repair at once. Do not operate the unit
until the leak is corrected. Failure to
comply with this procedure could result
in severe personal injury, death or sub-
stantial property damage.

c

Verify Flame Pattern and Combustion

Check the flame pattern through the
inspection port of the heat exchanger.
The flame should be blue and stable.
The flame should be the length of the
burner head openings.

The combustion testing and adjustments
must be performed by a qualified
installer, service agency or the gas suppli-
er. All combustion measurements must be
perform with calibrated equipment to
ensure proper reading and accuracy.

Test for CO2 or O2 and for CO during
high firing rate. To manually place the
boiler into high fire mode, reference
page 42, the combustion reading should
be within the range listed in Table 2.
The CO level should not exceed 100
ppm when combustion is correct.

The combustion levels should be mea-
sured at high firing rate, refer to page 42
of the PRESTIGE Excellence control
section on how to set the firing rate. If
the combustion levels are not within the
range given in Table 2 for the firing rate,
shut the boiler down and contact
Triangle Tube Engineering Department.
Failure to comply with this requirement
could result in severe personal injury,
death or substantial property damage.

c

Measure Input - Natural Gas Only

1. Ensure the boiler is firing at maximum firing

rate. To manually place the boiler into high
fire mode, reference page 42.

2. Operate the unit for approximately 10

minutes.

3. Turn off all gas appliances within the build-

ing, except the PRESTIGE Excellence.

4. At the gas meter, record the time required

to use one cubic foot of gas.

5. Calculate Natural gas input using the fol-

lowing equation:

3600 x 1000 / number of second recorded
for one cubic foot of gas = BTU/H.

6. The BTU/H calculated should approximate

the input rating listed on the unit.

WARNING

WARNING

WARNING

WARNING

O2 Min.

O2 Max.

CO2 Min.

CO2 Max.

CO Max

Natural Gas

2.30%

5.30%

8.80%

10.50%

100 ppm

Propane

2.70%

4.70%

10.70%

12.00%

100 ppm

Table 2: Recommended Combustion Levels