Installation - Domestic Piping

Domestic Piping

Union on domestic hot water outlet should be
piped at a higher elevation than domestic water
drain valve. This will make draining the water
heater easier.

Use dielectric unions or couplings to protect
hot and cold water fittings from corrosion
when connecting dissimilar materials such as
copper and galvanized iron pipe.

If copper pipe is used for domestic water con-
nections, first solder pipe to a threaded adapter
and then screw adapter into cold water inlet on
top of Excellence. Cold Water Inlet contains
an internal plastic dip tube which can be dam-
aged by heat from soldering.

Do not apply heat to the cold water inlet
when making sweat connections to water
heater. Sweat tubing to adapter before fit-
ting adapter to cold water inlet of heater. It
is imperative that no heat be applied to the
cold water inlet, as it contains a non metal-
lic dip tube.

When the water supply pressure is higher than
70 psig, it is recommended to install a pressure
reducing valve on cold water supply line to
prevent water loss through T&P relief valve.

Thermostatic Mixing Valve

The Excellence is factory supplied with a thermo-
static mixing valve with built-in check valve. The
mixing valve must be installed as shown in Fig. 1.

The operating range of the thermostatic mixing is
90ºF to 120ºF.

For applications with a domestic recirculation
loop, the recirculation pump should be controlled
by an aquastat. The maximum recommended set-
ting of the aquastat is 10ºF lower than the thermo-
static mixing valve setting.

For proper operation of the thermostatic
mixing valve and to prevent potential scald-
ing hazards, the recirculation loop should
be controlled by an aquastat. DO NOT use
continuous recirculation.

Recirculation Piping

Recirculation piping must be installed in the
cold water inlet as shown Fig. 5, page 9.

A stainless steel or bronze circulator is recom-
mended.

Storage Tank Application

For applications requiring large volumes of domes-
tic hot water in a relative short period, the installer
may include a storage type tank (see Fig. 6 page 10)
in the domestic piping.

The installer must:

1. Relocate the thermostatic mixing valve from

the Excellence to the outlet of the storage
tank.

2. Provide recirculation from the storage tank

back to the Excellence using a bronze type
circulator. Maximum recommended recircu-
lation flow rate is 1 gpm.

NOTICE

DANGER

Cold

Hot

Adapter

Check Valve

Mixed

Fig. 1: Mixing Valve Assembly