TriangleTube Prestige Excellence Part 1 User Manual

Page 95

Advertising
background image

14

Press STEP x5 -

P_10

Press STEP x6 -

P_11

Etc......

After Parameter 4 the display will show P followed
by a two-digit number that increases with each
press of the STEP button.

The actual parameter values displayed on
the unit may vary depending on the applica-
tion. The parameter sequence will always
occur in the order shown.

Once a particular parameter is reached, release the
STEP button. Wait a second and the display will
show the current setting for that parameter in the
right two display digits.

To Change a Parameter Setting

Use the + or - button to change the value of
the display.

Press the STORE button once to save the
change.

If a parameter setting is changed from the
factory default and the STORE button is not
pressed to save the setting, the MCBA mod-
ule will automatically store the setting after
15 minutes. Ensure all parameters settings
are either factory default or revised based
on the application. Review all parameters
settings on page 18 when completed and
prior to commission of the boiler. Failure to
comply could result in erratic or unreliable
operation of the Prestige boiler.

Once a parameter setting value has been
revised and stored, if the STEP button is
pressed for the next parameter setting the
value setting of that parameter will appear.
The display will not show P_XX of the next
sequential parameter. The sequence of
parameters may be scrolled through, as the
display will roll over from parameter 46 to
parameter 1.

If sequential parameters are being revised
and since the display will not show P_XX of
the sequential parameter, it is recommended
to press and hold the STEP button to scroll
through the entire list of parameters before
making any additional changes to avoid any
potential confusion.

WARNING

NOTICE

NOTICE

BEST PRACTICE

Water Heater Start-Up

Advertising