Water distribution, Problem solving, Ater – Bonaire / Celair (Tekelek) User Manual
Page 12: Istribution, Roblem, Olving
LP SERIES OWNER’S MANUAL
Unit Maintenance
TEK600 SERIES CONTROL
Page 12
W
ATER
D
ISTRIBUTION
Check the water distribution system for blockage. Check the delivery tube for kinks or
holes. Check that the clamps are secure and in place.
P
ROBLEM
S
OLVING
THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.
FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE RING
YOUR NEAREST CLIMATE TECHNOLOGIES SERVICE PROVIDER
PROBLEM
PROBABLE CAUSE
REMEDY
a
Black - out
a
Wait
b
Tripped Circuit Breaker
b
Reset
c
Blown Fuse
c
Replace
Unit fails to start
d
Electrical Fault
d
Call Climate Technologies
Service Provider
a
Pump Seized
a
Call Climate Technologies
Service Provider
Pump fails to start
b
Pump Burnt Out
b
Call Climate Technologies
Service Provider
a
Float Valve Leaking
a
Check adjustment or replace
seal
Water leaking from
overflow
b
Drain from Celdek Pads
b
Adjust Ball Valve level
a
Loose Delivery Tube
a
Check and tighten
b
Break in tubing
b
Replace as necessary
Water Droplets in air
stream
c
Pump Delivers Excessive
Water to Pads
c
Adjust the Dialflo to reduce
the flow
a
Inadequate Exhaust
a
Provide more open area to
exhaust stale air
Excessive humidity
b
Outside humidity high
b
Turn pump off may assist.
a
Dirty Filters
a
Clean
b
Dry Filters
b
Check water delivery
system. Adjust dialflo if
necessary.
Inadequate Cooling
c
Dialflo not set correctly
c
Adjust dialflo so that the
pads have even saturation.
a
Unit located near odour
source
a
Remove source
Unpleasant Odour
Rapid formation of
white deposits on
pads
High Mineral Content
Bleed off should be set at
maximum. More regular
maintenance may be
required. Dump valve may
be required for cyclic
dumping