LP SERIES OWNER’S MANUAL

Controls Setup & Commissioning

TEK600 SERIES CONTROL

Page 19

Entering the Parameter Setting Mode
To enter and adjust the parameter setting mode follow the instructions below:

1. Start with the wall switch in the off mode.

2. Press and hold the both the FAN and TIMER buttons together for 10 seconds.

3. Release both buttons and press the TIMER button once.

4. The 2hr light will turn on and the AUTO light will flash. At this point the control is

ready for any settings to be entered into the wall control.

Setting the dump delay
(2 hour light on and Auto light flashing)

1. To set the dump delay to dump 40 seconds after the pump turns off, rotate the dial

fully to the minimum position and the auto light will flash once every two seconds.

2. To set the dump delay to dump 1 hour after the pump has switched off, rotate the

dial fully to the maximum position and the auto light will flash twice every two
seconds.

3. Press

the

FAN button once to select the desired mode. (The fanlight will flash three

times to confirm the setting).

4. Press

the

AUTO button to go to the next setting (go to step 6) or press the TIMER

button to cancel.

Setting the Pre-cool.
(4 hour light on and Auto light flashing).

1. To disable the Pre-cool feature rotate the dial fully to the minimum position and the

auto light will flash once every two seconds.

2. To activate the Pre-cool feature rotate the dial fully to the maximum position and the

auto light will flash twice every two seconds.

3. Press the FAN button once to select the desired mode. (The fanlight will flash three

times to confirm the setting).

4. Press the AUTO button to go to the next setting or press the timer button to cancel.