LP SERIES OWNER’S MANUAL

Controls Setup & Commissioning

TEK600 SERIES CONTROL

Page 21

Reviewing Programmed Settings.
To review the settings entered into the Programmable Thermostat, enter the parameter
setting mode as explained from steps one to four on Page 19.
Once entering the parameter setting mode DO NOT ROTATE THE ADJUSTABLE DIAL.
Read the number of flashes from the AUTO light in with the two-hour light on.

1. Press

the

AUTO button once and the four-hour light will turn on, read the number of

flashes from the AUTO light.

2. Press

the

AUTO button once and the eight-hour light will turn on, read the number of

flashes from the AUTO light.

3. Press

the

AUTO button once and the two and four-hour lights will turn on, read the

number of flashes from the AUTO light.

If all settings are correct press the TIMER button to resume normal operation. If any
further adjustments need to be made go back to step one of the parameter settings.

Energizing the Dump Valve Solenoid to check the water level.
When a dump valve is fitted, the wall control is able to operate the dump valve solenoid
and pump independent of the fan operating so that the water level can be set, and
Dialflo adjustments can be made to the filter pads and bleed off.

1. Start with the wall switch in the off mode.

2. Press and hold the both the COOL and TIMER buttons together for 10 seconds.

Release both buttons and press the TIMER button once.

3. The four-hour light will flash once every two seconds to indicate that the dump valve

solenoid has been energized and is filling the base with water. The dump valve
solenoid will remain energized for ten minutes, after ten minutes the pump will start
automatically which then the bleed off and filter pad dialflo adjustments can be made.

4. If the installer does not want to wait ten minutes before the pump starts press the

AUTO button once to start the pump immediately.

5. The four-hour light will begin to flash twice every two seconds indicating that the

pump has been started.

6. To cancel this mode and return too normal operation press the TIMER button once. If

the timer button has not been pressed the pump will run for thirty minutes before
tuning itself off.