Controls Setup & Commissioning
TEK600 SERIES CONTROL
Page 13
Control Setup & Commissioning
Your evaporative air conditioner can be supplied with one of 2 control systems.
They are:
Manual
Low voltage control featuring basic control options.
Programmable
Thermostat
Low voltage control featuring basic control options and thermostat,
timed delayed starting and stopping, and dump valve features.
Connection
Cables
Low voltage controls are connected to the air conditioner control box
via a 20-metre low voltage loom.
NOTE:
Do not run the low voltage loom in long parallel runs with 240V
mains cables.
Keep the low voltage loom 200mm away from any long runs of mains
wiring.
Cross over mains wiring at right angles.
Do not use existing access holes in wall cavities where 240V mains
wiring exists. Drill a new access hole 200mm from the existing hole.
S
AFETY
•
Switch OFF the power and unplug the unit before touching any wiring or performing
any work.
•
A QUALIFIED ELECTRICIAN must carry out all 240-volt electrical work.
B
EFORE
C
OMMENCING
Packaging
Upon delivery, check that there is no damage to the unit. Any damage should be
reported to your nearest Climate Technologies sales outlet.
Is the control system correct?
Check the customer order to ensure that you have all the correct equipment for
installation.