Pipe sizes, Temperature pressure relief valve, Expansion control valve – AquaMAX G135VE User Manual

Page 30

Advertising
background image

CONNECTIONS – PLUMBING

30

PIPE SIZES

To achieve true mains pressure operation, the cold water line to the water heater
should be the same size or bigger than the hot water line from the water heater.

The pipe sizing for hot water supply systems should be carried out by persons
competent to do so, choosing the most suitable pipe size for each individual
application. Reference to the technical specifications of the water heater and
local regulatory authority requirements must be made.

TEMPERATURE PRESSURE RELIEF VALVE

The temperature pressure relief valve is shipped behind the front cover. The
temperature pressure relief valve must be fitted before the water heater is
operated. Before fitting the relief valve, make sure the probe has not been bent.
Seal the thread with an approved thread sealant such as Teflon tape - never
hemp. Make sure the tape does not hang over the end of the thread.

Screw the valve into the correct opening (

refer to the installation diagram

on

page 27) leaving the valve drain pointing downwards. Do not use a wrench on
the valve body - use the spanner flats provided. A copper drain line must be fitted
to the temperature pressure relief valve (refer to "

Relief Valve Drain"

on page 31).


The valve must be insulated with closed cell polymer insulation or similar
(minimum thickness 9 mm) and the insulation installed so as not to impede the
operation of the valve. The insulation must be weatherproof and UV resistant if
exposed.

EXPANSION CONTROL VALVE

Local regulations may make it mandatory to install an expansion control valve
(ECV) in the cold water line to the water heater. In other areas, an ECV is
required if the saturation index is greater than +0.4 (refer to

“Water Supplies”

on

page 13).

The expansion control valve must always be installed after the non-return valve
and be the last valve installed prior to the water heater (

refer to diagram

on

page 29). A copper drain line must be fitted to the expansion control valve (refer
to

"Relief Valve Drain"

on page 31).


The valve, if installed within 500 mm of the water heater, must be insulated with
closed cell polymer insulation or similar (minimum thickness 9 mm) and the
insulation installed so as not to impede the operation of the valve. The insulation
must be weatherproof and UV resistant if exposed.

Advertising