CONNECTIONS – PLUMBING

31

RELIEF VALVE DRAIN

DN15 copper drain lines must be fitted to the temperature pressure relief valve
and expansion control valve (if one is installed) to carry the discharge clear of
the water heater. Connect the drain lines to the valves using disconnection
unions. The drain line from the valve to the point of discharge should be as short
as possible, have a continuously downward fall all the way from the water heater
to the discharge outlet and have no tap, valves or other restrictions in the pipe
work.

A drain line from a relief valve must comply with the requirements of
AS/NZS 3500.4.

A drain line must be no longer than 9 metres with no more than three bends
greater than 45° before discharging at an outlet or air break. The maximum
length of 9 metres for a drain line is reduced by 1 metre for each additional bend
required of greater than 45°, up to a maximum of three additional bends. Where
the distance to the point of final discharge exceeds this length, the drain line can
discharge into a tundish.

Subject to local regulatory authority approval, the drain lines from the
temperature pressure relief valve and expansion control valve from an individual
water heater may be interconnected.

The outlet of a drain line must be in such a position that flow out of the pipe can
be easily seen, but arranged so discharge will not cause injury, damage or
nuisance. The termination point of a drain line must comply with the requirements
of AS/NZS 3500.4. Drain lines must not discharge into a safe tray.

In locations where water pipes are prone to freezing, drain lines must be
insulated, must not exceed 300 mm in length and are to discharge into a tundish
through an air gap of between 75 mm and 150 mm.

If a drain line discharges into a tundish, the drain line from the tundish must be
not less than DN20. The drain line from a tundish must meet the same
requirements as for a drain line from a relief valve.

Warning: As the function of the temperature pressure relief valve on this

water heater is to discharge high temperature water under certain conditions, it
is strongly recommended the pipe work downstream of the relief valve be
capable of carrying water exceeding 93°C. Failure to observe this precaution
may result in damage to pipe work and property.