SECTION 3 • IMPLEMENTATION TABLE

DNP Implementation Table

Table 3-1 identifies which object variations, function codes, and qualifiers the BE1-851E DNP supports in

both request messages and in response messages.
Static (non-change-event) object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded to

with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded to with

qualifiers 17 or 28.
Change-event objects are always responded to with qualifiers 17 and 28.

Table 3-1. BE1-851E DNP Implementation Table

OBJECT

REQUEST

(BE1-851E will parse)

RESPONSE

(BE1-851E will respond with)

Object

No.

Variation

No.

Description

Function

Codes (dec)

Qualifier Codes

(hex)

Function

Codes (hex)

Qualifier Codes

(hex)

1

0

Binary Inputs - (Variation 0 is

used to request default

variation)

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

1

1

(default -

see note 1)

Single-Bit Binary Input

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

(response)

00,01 (start-stop)
17,28 (index)

2

0

Binary Input Change

(Variation 0 is used to request

default variation)

1 (read)

06 (no range)

07,08 (limited qty)

2

1

Binary Input Change without

time

1 (read)

06 (no range)

07,08 (limited qty)

81

(response)

17,28 (index)

2

2

(default -

see note 1)

Binary Input Change with time 1 (read)

06 (no range)

07,08 (limited qty)

81

(response)

17,28 (index)

10

0

Binary Output - (Variation 0 is

used to request default

variation)

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

10

2

(default -

see note 1)

Binary Output Status

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

12

1

Control Relay Output Block

3 (select)
4 (operate)
5 (direct op)
6 (dir op Noack)

00,01 (start-stop)

07,08 (limited qty)

17,28 (index)

81

echo of request

30

0

Analog Input (Variation 0 is

used to request default

variation)

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81(response) 00,01 (start-stop)

17,28 (index)

30

1

32-Bit Analog Input With Flag 1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

30

2

16-Bit Analog Input With Flag 1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

30

3

(default -

see note 1)

32-Bit Analog Input Without

Flag

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

9289900792 Rev C