Basler Electric BE1-851E DNP3 Protocol User Manual

Page 25

Advertising
background image

Point

Index

Description

Control Codes And Their Description

26

Local Setting Group Control Switch

Latch On: Return Setting Group Control

to relay local logic

27

101 Virtual Breaker Control Switch

Close:

Close Breaker (changes 101C

Binary Input from 0 to 1 for 200

ms )

Trip:

Trip Breaker (changes 101T

from 0 to 1 for 200 ms)

Notes for Table 5-2:

1. Read of Points

- Reads of points from 0 to 7, 9 to 16, and 18 to 26 return the current state of corresponding

point.

- Reads of points from 8, 17, and 27 always return zero.

2- The following restrictions should be observed when using object 12 to control the points listed in

Table 5-1.

• The Control Code field of object 12 is parsed the following way:

- If the Control Code is NULL, then the command will be accepted without any action being

taken.

- If Queue, and Clear sub-fields are not zero, the returned Control Status is 4 (Control

operation not supported).

- A Code sub-field of “Pulse On” (1) in combination with a value in the Trip/Close sub-field

form a “Trip” or “Close” value. A “Trip” value consists of a “PULSE ON” (1) in the Code

sub-field and a 2 in the Trip/Close sub-field. This results in a value of 81(hex) in the

Control Code field. A “Close” value consists of a “PULSE ON” (1) in the Code sub-field

and a 1 in the Trip/Close sub-field. This results in a value of 41 (hex) in the Control Code

field.

3. Valid Control Code values are:

- 0x00 = No action will be taken.

- 0x01 = Pulse output to opposite of current state, and then restore to previous state. Pulsed

output is active 200 to 250 ms.

- 0x03 = Latch On

- 0x04 = Latch Off

- 0x41 = Close (Breaker Close)

- 0x81 = Trip (Breaker Open)

All operations not defined above are invalid and will be rejected. If the Control Code is legal, but not

supported for the requested point, the Status Return value is “Control operation not supported for this

point” (value 4).

- The Count, OnTime and OffTime fields are ignored.

- Arm timer value for all Select/Operate operations is 30 seconds.

It is important to notice that any control function may be rejected because of the relay internal state.

When this happens, the Status Return value is “Request not accepted because of hardware

problems” (value 6). One of the reasons for the rejection may be that that point Logic Function Block

has the Logic (Control) Mode disabled.
For example: Control functions for the hardware output points (points 0 to 13) will be rejected if the

Output Control for all hardware outputs is disabled.
The Logic (Control) Mode of any object 12 point can be changed (enabled/disabled) via the specific

point of object 41 (Analog Output Control Blocks). Refer to Analog Output Status Points and Analog

Output Control Block points from 0 to 6.

9289900792 Rev C

BE1-851E DNP Protocol

5-5