Appendix for Binary Output Status Points and Control Relay Output

Blocks

To enable Master which can support only Trip and Close commands to control BE1-851E Control Relay

Output Block points, second way of controlling Control Relay Output Blocks is added as presented in

Table 5-3.
User can select old (legacy) Control Relay Output Blocks (Table 5-2) or a new (Table 5-3) via DNP object

41 point 24. Selection stays remembered in non-volatile memory. When Table 5-2 is selected, object 40,

point 24 has value 1. When Table 5-3 is selected, object 40, point 24 has value 2. When selecting specific

Control Relay Output Blocks table, object 41, point 24 must be set to 1 or 2 via function codes

select/operate or only direct operate or direct operate, noack.

Notes:

- Old Control Relay Output Blocks (Table 5-2) has 27 points while new Control Relay Output

Blocks (Table 5-3) has 38. The additional 11 points are added as single function points to support

only pulsing control. New Control Relay Output Blocks (Table 5-3) has only complementary or

single function indices and is DNP compliant.

- Reading values of points 0 to 27 are the same in the both Control Relay Output Blocks tables.

Reading values of points 28 to 40 in the new Control Relay Output Blocks (Table 5-3) are the

same as for points 0 to 8, and points 37 to 40 have the same reading values as points 18 to 21.

Table 5-3. Appendix for Binary Output Status Points and Control Relay Output Blocks

Binary Output Status Points:

Object Number: 10

Variations supported: 2

Request Function Codes supported: 1(read)

Default Variation reported when variation 0 requested:2(Binary Output Status)

Control Relay Output Blocks

Object Number: 12

Variations supported: 1

Request Function Codes supported: 3(select), 4(operate),5(direct operate), 6(direct operate, noack)

Point

Index

Description

Complementary

(C) or

Single (S)

Function Index

Permitted Codes

0

Hardware Output A -

Latch control

C

0x03(Latch On/NUL) or

0x41(PulseOn/Close) sets output to

state 1

0x04 (Latch Off/NUL) or

0x81(PulseOn/Trip) sets output to state 0

1

Hardware Output 1- Latch

control

2

Hardware Output 2-

Latch control

3

Hardware Output 3 - -

Latch control

4

Hardware Output 4 -

Latch control

5

Hardware Output 5 -

Latch control

6

Hardware Output 6 -

Latch control

7

Hardware Output 7 -

Latch control

8

All Hardware Outputs’ -

Latch control

5-6

BE1-851E DNP Protocol

9289900792 Rev C