Point

Index

Description

Complementary

(C) or

Single (S)

Function Index

Permitted Codes

9

Hardware Output A Local

Control

S

0x03(Latch On/NUL) or

0x41(PulseOn/Close) sets output to

relay logic

10

Hardware Output 1 Local

Control

11

Hardware Output 2 Local

Control

12

Hardware Output 3 Local

Control

13

Hardware Output 4 Local

Control

14

Hardware Output 5 Local

Control

15

Hardware Output 6 Local

Control

16

Hardware Output 7 Local

Control

17

All Hardware Outputs’ Local

Control

18

43 Selector Switch Status -

Latch control

C

0x03(Latch On/NUL) or

0x41(PulseOn/Close) sets Selector

Switch to 1

0x04 (Latch Off/NUL) or

0x81(PulseOn/Trip) sets Selector Switch

to 0

19

143 Selector Switch Status -

Latch control

20

243 Selector Switch Status -

Latch control

21

343 Selector Switch Status -

Latch control

22

Setting Group 0

S

0x03(Latch On/NUL) or

0x41(PulseOn/Close) selects group

to be active

23

Setting Group 1

24

Setting Group 2

25

Setting Group 3

26

Local Setting Group Control

Switch

S

0x03(Latch On/NUL) or

0x41(PulseOn/Close) returns Setting

Group Control to relay local logic

27

101 Virtual Breaker Control

Switch

C

0x41(PulseOn/Close) Close breaker

0x81(PulseOn/Trip) Trip breaker

28

Hardware Output A - Pulse

Control

S

0x81(Pulse On/Trip) or

0x01(Pulse On/NUL)

Pulse output / Selector switch to opposite

of current state then restore

to previous state(pulsed output is active

200 to 250 ms)

29

Hardware Output 1 - Pulse

Control

30

Hardware Output 2 -Pulse

Control

31

Hardware Output 3 -Pulse

Control

32

Hardware Output 4 -Pulse

Control