Table 5-9. Analog Output Status Points and Control Blocks

Analog Output Status Points

Object Number: 40

Variations Supported: 1, 2

Request Function Codes supported: 1 (read)

Default Variation Reported When Variation 0 Requested: 1 (32-Bit Analog Output Status)

Analog Output Blocks

Object Number: 41

Variations Supported: 1, 2

Request Function Codes supported: 3(select), 4(operate), 5(direct operate), 6 (direct operate, noack)

Index

Description

Notes

0

Hardware Output Logic Control Mode

1,2

1

43 Aux Virtual Switch Logic Mode

1,3

2

143 Aux Virtual Switch Logic Mode

1,3

3

243 Aux Virtual Switch Logic Mode

1,3

4

343 Aux Virtual Switch Logic Mode

1,3

5

Active Setting Group Control Mode

1,4

6

101 Breaker Control Switch Mode

1,5

7

Target Status Reset Control

6

8

Major Alarms Reset

7

9

Minor Alarms Reset

7

10

Logic Alarms Reset

7

11

Relay Trouble Alarms Reset

8

12

Breaker Accumulated Duty for Phase A

9

13

Breaker Accumulated Duty for Phase B

9

14

Breaker Accumulated Duty for Phase C

9

15

Breaker Operation Counter

10

16

Peak Demand Current Since Reset - Phase A

11

17

Peak Demand Current Since Reset - Phase B

11

18

Peak Demand Current Since Reset - Phase C

11

19

Peak Demand Current Since Reset - Neutral

11

20

Peak Demand Current Since Reset - Negative Sequence

11

21

Fault Number for Selected Fault Summary Report

12

22

Synchronization Time Period

13

23

Current Dead Band

14

24

‘Control Relay Output Blocks’ Table Selection

15

Notes for Table 5-9:

1. This data is a setting and takes effect after being saved to non-volatile memory.

Procedure of saving data to non-volatile memory is performed only once per request for all points

requested to be changed through function Operate(4), Direct Operate(5) or Direct Operate

Noack (6).
Saving to a non-volatile memory is not implemented per point basis because it would significantly

prolong requested message processing time and cause response time-out. It is important to note

that object 12 (Binary Output Status ) points from 0 to 23 can be successfully controlled only if

their function blocks mode are enabled in the time of parsing. This is the reason that

in the same

9289900792 Rev C

BE1-851E DNP Protocol

5-15