8-Bit Unsigned Integer, Object 102

Table 5-12 is the point list for Object 102, and lists the 8-Bit Unsigned Integer Points. Note that this object

has only variation 1 and cannot be requested with default variation 0.

Table 5-12. Object 102, 8-Bit Unsigned Integer Points

8-Bit Unsigned Integer

Object Number: 102

Variations Supported: 1

Request Function Codes supported: 1 (read)

Index

Description

0 - 9

Model Number

10 - 28

Application Software Version Number and Date

29 - 47

Boot Software Version Number and Date

48 - 61

Serial Number

62 - 83

Style Number

84 - 99

Part Number

100 - 131

Relay ID

132 - 163

Station ID


Explanation:
Each point represents one character of a particular string.

Example: To read the Model Number, which is “BE1-851E”, the returned read value for points 0 to 9 are:

Point

0

1

2

3

4

5

6

7

8

9

Read Value in

ASCII format

B

E

1

-

8

5

1

Null

Null

Null

Object 102 is not included in Class 0 poll response.