Basler Electric BE1-851E DNP3 Protocol User Manual

Page 14

Advertising
background image

OBJECT

REQUEST

(BE1-851E will parse)

RESPONSE

(BE1-851E will respond with)

Object

No.

Variation

No.

Description

Function

Codes (dec)

Qualifier Codes

(hex)

Function

Codes (hex)

Qualifier Codes

(hex)

30

4

16-Bit Analog Input Without

Flag

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

32

0

Analog Change Event

(Variation 0 is used to request

default variation)

1 (read)

06 (no range)

07,08 (limited qty)

32

1

(default -

see note 1)

32-Bit Analog Input without

time

1 (read)

06 (no range)

07,08 (limited qty)

81

17,28 (index)

32

2

16-Bit Analog Input without

time

1 (read)

06 (no range)

07,08 (limited qty)

81

17,28 (index)

32

3

32-Bit Analog Input with time 1 (read)

06 (no range)

07,08 (limited qty)

81

17,28 (index)

32

4

16-Bit Analog Input with time 1 (read)

06 (no range)

07,08 (limited qty)

81

17,28 (index)

40

0

Analog Output Status -

(Variation 0 is used to request

default variation)

1

00,01 (start-stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

40

1

32-bit Analog Output Status

1 (read)

00,01 (start-stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

40

2

(default -

see note 1)

16-bit Analog Output Status

1 (read)

00,01 (start-stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

41

1

32-bit Analog Output Block

3 (select)

4 (operate)

5 (direct op)

6 (dir op noack)

00,01 (start-stop)

07,08 (limited qty)

17,28 (index)

81

echo of request

41

2

16-bit Analog Output Block

3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)

00,01 (start-stop)

07,08 (limited qty)

17,28 (index)

81

echo of request

50

1

Time and Date

1 (read)
2 (write)

00,01 (start-stop)

06 (no range or all)

07 (limited qty=1)

08 (limited qty)

17,28 (index)

81

00,01 (start-stop)
17,28 (index)

60

1

Class 0 Data (Note 1) (Note 4) 1 (read)

06 (no range or all)

81

60

2

Class 1 Data

1 (read)

06 (no range or all)

07,08 (limited qty)

81

60

3

Class 2 Data

1 (read)

06 (no range or all)

07,08 (limited qty)

81

60

4

Class 3 Data

1 (read)

06 (no range or all)

07,08 (limited qty)

81

80

1

Internal Indications

2 (write)

00 (start-stop)

(index must=7)

102

1

8-Bit Unsigned Integer (Note

2)

1 (read)

00,01 (start- stop)

06 (no range)

07,08 (limited qty)

17,28 (index)

81(response) 00,01 (start-stop)

17,28 (index)

No Object(function code only)

(See Note 3)

13 (cold restart)

No Object(function code only)

(See Note 3)

14 (warm

restart)

No Object (function code only) 23 (delay meas)

3-2

BE1-851E DNP Protocol

9289900792 Rev C